Plan Review Notes
Plan Review Notes For Permit 99121671
Permit Number 99121671
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-FOOTING F2 TO BE 16" DEEP MINIMUM.
 SECTION 1804.1.3 SBC 1997 AND CITY
 AMENDMENTS.
 3-REAR ELEVATION EXCEEDS THE ALLOWED
 OPENING PERCENTAGE. TABLE 600 SBC 1997
 4-CLARIFY/REVISE FLOOR PLANS AND
 ELEVATIONS TO MATCH EACH OTHER.
 -BE SPECIFIC WITH OPTIONS ON THIS HOUSE
 -SEE COMMENTS ON ALL PLANS AND UPDATE/
 REVISE AS REQUIRED.
 5-WINDOW AT BEDROOM #2 DOESN'T MEET THE
 EGRESS REQUIREMENTS. SECTION 1005.4.4
 SBC 1997.
 -SAME FOR MASTER BEDROOM WINDOW.
 6-A/C FLOOR AREA IN ENERGY CALCULATIONS
 DOESN'T MATCH PLANS.
 7-REVISE/CLARIFY SIZE OF SPREAD FOOTINGS
 SEE SOIL TEST REPORT FOR RECOMMENDED
 MINIMUM DEPTH.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITES ASSEMBLY AND
 GARAGE DOORS.
 9-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS (OR SEPARATE PERMIT)
 10-FLOOD ZONE "A8" AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
 11-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT FRONT PORCH.
 SECTION 104.2 CITY AMENDMENTS.
 12-PROVIDE COMPLETE BUCK DETAILS FOR
 EXTERIOR DOORS, WINDOWS AND GARAGE
 DOOR.
 13-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS. SEC. 2405.2 SBC 1997.
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.