| 2001-01-08 00:00:00 | *************UNSAT******************** | | | | | | 1)NOTE:NEED TO SUBMTI AIC RATING OF ALL | | | EQUIPMENT MAINS. 110-9/230-65 | | | | | | 2)NOTE: NEED TO COMPLY WIHT REQ`MENTS | | | OF SMOKE DETECTORS INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. AS PER 1993/1996 | | | NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. PLEASE SHOW. | | | | | | 4)NOTE:PLEASE LIST REQ`D BATH(S) CIRCUT | | | ON PANEL SCHDULE. AS PER 210-52D | | | | | | 5)NOTE:PLEASE INCLUDE BLDG.STEEL ON | | | RISER DIAGRAM AS PART OF THE GROUNDING | | | ELECTRODE SYSTEM.250-81/215-5 | | | | | | 6)NOTE:AS PER 110-16 A/C DISC. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 65908096 EXT 8372 |
|