| 2001-01-08 00:00:00 | COMPLY W/ALL PREVIOUS COMMENTS DATED |
| | 3/2/00 IN ADDITION TO THE FOLLOWING: |
| | |
| | SUBMIT COPY OF APPROVAL FORM FROM CITY |
| | OF WPB FOR SIZE OF GREASE INTERCEPTOR. |
| | CONTACT R.COMPO AT (561)835-7423. |
| | |
| | SHOW LOCATION OF THE GAS LINE ON CIVIL |
| | DRAWINGS AND CLEARLY SHOW ENTRANCE POINT |
| | INTO BUILDING.PIPING SHALL ONLY BE RUN |
| | UNDER BUILDING SLAB WHEN NO OTHER METHOD |
| | IS AVAILABLE.DETERMINATION SHALL BE MADE |
| | CONTINGENT ON ADDITIONAL INFORMATION. |
| | SGC SEC.308.3,308.3.2. |
| | |
| | TWO WAY CLEANOUTS SHALL BE INSTALLED ON |
| | THE WASTE LINES LEADING TO AND FROM THE |
| | GREASE INTERCEPTOR.SPC 710.4. |
| | |
| | WATER RISER CONTROL VALVES SHALL BE |
| | ACCESSIBLE AND NOT LOCATED IN ROOMS PER |
| | SPC SEC.610.4.2. |
| | |
| | MANUFACTURER'S DATA SHEETS FOR SOVENT |
| | SYSTEM COMPONENTS SHALL BE SUBMITTED FOR |
| | REVIEW PRIOR TO ROUGH PLUMBING INSPECT- |
| | ION PER SPC SEC.923.3,COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1. |
| | |
| | SHT.P-002 SUBMIT PIPNG DETAILS FOR WATER |
| | HEATER PER COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1.INCLUDE FLUE DETAILS . |
| | |
| | OVERFLOW DRAINS FOR ROOF SHALL TERMINATE |
| | ABOVE GRADE AT AN OBSERVABLE POINT PER |
| | SPC SEC.1109.2. |
| | |
| | SHT.A-9.4-FLOOR PLAN OF RESTROOM ON ROOF |
| | DOESN'T CORRELATE W/ELEVATION DETAIL |
| | #16. |
| | |
| | SHT.A-9.4-HEIGHT OF ACCESSIBLE LAV.SHALL |
| | COMPLY W/FACBC SEC.4.19.2. |
| | |
| | FLUSH CONTROLS FOR WATER CLOSETS SHALL |
| | BE INSTALLED ON THE WIDE SIDE OF TOILET |
| | AREA PER FACBC SEC.4.16.5.AND URINALS |
| | SHALL COMPLY W/FACBC SEC.4.18.4. |
| | |
| | PLEASE CALL (561)659-8096,EXT.8377 IF |
| | YOU HAVE ANY QUESTIONS. |
| | TIMOTHY LARGE-PLUMBING PLANS EXAMINER. |