| 2001-01-08 00:00:00 | JOB SPEC.15420-12-SEC.3.9-(C)(E)(F)(G). |
| | PIPING SUPPORTS SHALL COMPLY W/SPC SEC. |
| | 310.3. |
| | |
| | JOB SPEC.15430-17-SEC.3.1.(W) AND |
| | 15430-22-SEC.3.9(A)-GREASE RECOVERY |
| | UNITS ARE NOT PERMITTED PER CITY ORD. |
| | |
| | JOB SPEC.15430-21-SEC.3.8-GREASE INTER. |
| | SHALL COMPLY W/CITY OF WPB UTILITIES |
| | REQS.CONTACT R.COMPO AT (561)835-7423. |
| | |
| | JOB SPEC.15486-6-SEC.3.2(G)-RELIEF VALVE |
| | DRAIN SHALL DISCHARGE TO EXTERIOR PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.3 |
| | |
| | SHT.L-104-LOCATION OF BACKFLOW PREVENTER |
| | SHALL BE DETERMINED BY CITY OF WPB |
| | UTILITIES DEPT.CALL (561)659-8000. |
| | |
| | HANDICAP ACCESSIBLE ROOMS SHALL W/FACBC |
| | SECS.9.1-9.4 AND ALSO W/FACBC SEC.9.2.3 |
| | (FLA.5% RULE). |
| | |
| | CLEARLY NOTE THE TOTAL NUMBER OF SLEEP- |
| | ING ROOMS IN THE FACILITY. |
| | |
| | SHT.A-2.1.-LOCATION OF GREASE TRAP SHALL |
| | COMPLY W/CITY OF WEST PALM BEACH |
| | UTILITIES REQS.CONTACT R.COMPO AT (561) |
| | 835-7423.COMPLY W/SBC SEC.1803.1.3. |
| | |
| | SHT.A-2.1.-LOCATION OF BACKFLOW |
| | PREVENTER SHALL BE DETERMINED BY CITY |
| | OF WPB UTILITIES.CALL (561)659-8000 |
| | |
| | THE ACCESSIBLE (HANDICAP) UNITS SHALL BE |
| | DISPERSED AMONG THE VARIOUS FLOORS AND |
| | CLASSES PER FACBC SEC.9.1.4(1). |
| | |
| | ALL PUBLIC AND COMMON USE AREA ROOMS |
| | SHALL BE FULLY ACCESSIBLE. |
| | |
| | SUBMIT DETAIL OF ELEC.WATER COOLER ON |
| | ROOF. COMPLY W/FACBC SEC.4.1.3.(10)(A), |
| | 4.15 AND FIGURE 27. |
| | |
| | SHT.M-4 SHOWS OVERFLOW FROM COOLING |
| | TOWERS AND CHEMICAL FEEDER TO SANITARY. |
| | PH OF EFFLUENT SHALL COMPLY W/SPC SEC. |
| | 701.5.(DATA FROM MANUF.REQD.INDICATING |
| | PH LEVEL OF EFFLUENT AT POINT OF |
| | DISCHARGE.) |
| | |
| | PANS AND PAN DRAINS ARE REQD.FOR THE |
| | WATER HEATERS PER COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.507.8.1. |
| | |
| | SUBMIT COMPLETE ISOMETRIC FOR THE U/G |
| | SANITARY SYSTEM DRAWN IN COMPLIANCE W/ |
| | ASSE STANDARD #1043 FOR THE SOVENT |
| | SYSTEM.(LOCATION OF PRL AND CONNECTIONS |
| | TO SYSTEM,REQD.DISTANCES FROM STACK,ETC. |
| | |
| | SHOW LOCATION OF WATER TREATMENT SYSTEM |
| | ON PLANS. |
| | |
| | FIXTURE REQS.FOR RESTAURANT SHALL COMPLY |
| | W/SPC TABLE 407 & F.S.553.141-POT.PARITY |
| | |
| | SUBMIT COMPLETE GAS DRAWING FOR REVIEW. |
| | SHOW ALL CUT SECTIONS OF PIPE,SIZES,COM- |
| | BUSTION AIR,VENT DETAIL,METER LOC.COMPLY |
| | W/SGC SECS.305.4,402.1,402.4,NFPA 54. |
| | |
| | CLEARLY SHOW HOW EFFLUENT FROM PUMPS IN |
| | ELEVATOR SHAFT WILL BE DISPOSED. |
| | |
| | DRAIN AT DUMPSTER AREA SHALL DISCHARGE |
| | THRU GREASE INTERCEPTOR PER SPC SEC. |
| | 1004.1. |
| | |
| | SHT.A7.3-ROOF STRAINERS ON ROOF DRAINS |
| | SHALL COMPLY W/SPC SEC.1107.2. |
| | |
| | SHT.A9.4-MAX.HEIGHT OF URINAL RIM SHALL |
| | BE 17" AFF PER FACBC SEC.4.18.2. |
| | |
| | SHT.A9.4-LAV.IN H.C.STALL INFRINGES ON |
| | CLEAR FLOOR SPACE FOR WATER CLOSET. |
| | COMPLY W/FACBC SEC.4.17.3. |
| | |
| | MIN.OF 29"IS REQD.UNDER H.C.LAV.TO FF |
| | PER FACBC SEC.4.19.2. |
| | |
| | SHTS.P-002 AND P-400 NOTE TWO(2) |
| | DIFFERENT TYPES OF INTERCEPTORS.CLARIFY. |
| | |
| | SEE PLUMBING REVIEW STEP#4 FOR CONTIN- |
| | UATION OF PLUMBING COMMENTS. |