Plan Review Notes
Plan Review Notes For Permit 99121640
Permit Number 99121640
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00JOB SPEC.-15420-12-SEC.3.9 (E)(F)(G)
 PIPING SUPPORTS SHALL COMPLY W/SPC SEC.
 310.3.
  
 JOB SPEC.15430-17-SEC.3.1(W) AND
 15430-22-SEC.3.9(A)-GREASE RECOVERY
 UNITS ARE NOT PERMITTED PER CITY ORD.
  
 JOB SPEC.15430-21-SEC.3.8-GREASE INTER.
 SHALL COMPLY W/HEALTH DEPT.REQS.CHAPT.
 64E-6.013(5)
  
 JOB SPEC.15486-6-SEC.3.2(G)-RELIEF VALVE
 DRAIN SHALL DISCHARGE TO EXTERIOR PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.3
  
 SHT.L-104-LOCATION OF BACKFLOW
 PREVENTION DEVICE SHALL BE DETERMINED BY
 CITY OF WPB UTILITIES DEPT.CALL
 CALL (561)659-8000.
  
 HANDICAP ACCESSIBLE ROOMS SHALL COMPLY
 W/FACBC SEC.9.1-9.4.AND ALSO W/FACBC
 SEC.9.2.3(FLA.5% RULE)
  
 CLEARLY SHOW THE TOTAL NUMBER OF ROOMS
 IN THE STRUCTURE.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.
  
 SHT.A-2.1-LOCATION OF GREASE TRAP SHALL
 COMPLY W/HEALTH DEPT.REQS.
 CHAPT.64E-6.013(5) AND SPC SEC.1803.1.3.
  
 SHT.A-2.1-LOCATION OF BACKFLOW PREV.
 DEVICE SHALL BE DETERMINED BY CITY OF
 WPB UTILITIES .CALL (561)659-8000.
  
 CLEARLY SHOW LENGTH AND WIDTH OF TYPICAL
 SHOWER AND HANDICAP SHOWER STALL.COMPLY
 W/FACBC SECS.4.21-4.21.8.
  
 THE ACCESSIBLE (HANDICAP)UNITS SHALL BE
 DISPERSED AMONG THE VARIOUS CLASSES AND
 FLOORS PER FACBC SEC.9.1.4.(1).
  
 SHOW TYPICAL CLEARANCE FOR WATER CLOSETS
 PER SPC SEC.403.4.& FACBC FIG.28 FOR
 ACCESSIBLE UNITS.
  
 ALL PUBLIC AND COMMON USE AREA TOILET
 ROOMS SHALL BE FULLY ACCESSIBLE PER
 FACBC SEC.4.1.3.(11),9.1.
  
 SUBMIT DETAILS ON SCUPPERS (LXW) AND
 CALCULATIONS FOR OVERFLOW (SECONDARY)
 DRAINAGE.COMPLY W/SBC SEC.1517.6.4.,
 1517.6.4.2.,1517.6.4.3.,SPC 1108.2.2,
 1108.3.
  
 SECONDARY DRAIN SYSTEM SHALL COMPLY W/
 SPC 1109.2,1109.3,AND APPENDIX"A".(THE
 OVERFLOW SYSTEM IS INADEQUATE PER NOTED
 CODE SECS.)
  
 LENGTH OF GRAB BARS BEHIND WATER CLOSETS
 SHALL COMPLY W/FACBC SEC.4.16.4.
  
 SHT.A9.4-DETAIL #12-H.C.WATER TO BE 18"
 FROM WALL.FACBC FIG.30.
  
 FLOORS AND WALLS IN COMMON/PUBLIC AREA
 RESTROOMS SHALL COMPLY W/SBC SEC.1204.2
  
 DRINKING FOUNTAIN ON ROOF SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).
  
 SHT.M-4-SHOWS OVERFLOW FROM COOLING
 TOWERS AND CHEMICAL FEEDER TO SANITARY.
 PH OF EFFLUENT SHALL COMPLY W/SPC SEC.
 701.5.(DATA FROM MANUF.REQD.INDICATING
 PH LEVELOF EFFLUENT AT POINT OF
 DISCHARGE.)
  
 PANS AND PAN DRAINS ARE REQD.FOR THE
 WATER HEATERS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.507.8.1.
  
 SUBMIT U.L.ASSEMBLY NUMBERS FOR FIRE
 SAFING DETAILS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.4.(SEE SHT.P-400)
  
 SUBMIT COMPLETE ISOMETRIC FOR THE U/G
 SANITARY SYSTEM DRAWN IN COMPLIANCE W/
 ASSE STANDARD #1043 FOR SOVENT SYSTEM.
  
 SHOW LOCATION OF WATER TREARMENT SYSTEM
 ON PLAN.
  
 SEE PLBG.REVIEW STEP#2 FOR CONTINUATION
 OF COMMENTS.1/19/00.