| Date |
Text |
| 2001-01-08 00:00:00 | JOB SPEC.-15420-12-SEC.3.9 (E)(F)(G) |
| | PIPING SUPPORTS SHALL COMPLY W/SPC SEC. |
| | 310.3. |
| | |
| | JOB SPEC.15430-17-SEC.3.1(W) AND |
| | 15430-22-SEC.3.9(A)-GREASE RECOVERY |
| | UNITS ARE NOT PERMITTED PER CITY ORD. |
| | |
| | JOB SPEC.15430-21-SEC.3.8-GREASE INTER. |
| | SHALL COMPLY W/HEALTH DEPT.REQS.CHAPT. |
| | 64E-6.013(5) |
| | |
| | JOB SPEC.15486-6-SEC.3.2(G)-RELIEF VALVE |
| | DRAIN SHALL DISCHARGE TO EXTERIOR PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.3 |
| | |
| | SHT.L-104-LOCATION OF BACKFLOW |
| | PREVENTION DEVICE SHALL BE DETERMINED BY |
| | CITY OF WPB UTILITIES DEPT.CALL |
| | CALL (561)659-8000. |
| | |
| | HANDICAP ACCESSIBLE ROOMS SHALL COMPLY |
| | W/FACBC SEC.9.1-9.4.AND ALSO W/FACBC |
| | SEC.9.2.3(FLA.5% RULE) |
| | |
| | CLEARLY SHOW THE TOTAL NUMBER OF ROOMS |
| | IN THE STRUCTURE.COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.104.2.1. |
| | |
| | SHT.A-2.1-LOCATION OF GREASE TRAP SHALL |
| | COMPLY W/HEALTH DEPT.REQS. |
| | CHAPT.64E-6.013(5) AND SPC SEC.1803.1.3. |
| | |
| | SHT.A-2.1-LOCATION OF BACKFLOW PREV. |
| | DEVICE SHALL BE DETERMINED BY CITY OF |
| | WPB UTILITIES .CALL (561)659-8000. |
| | |
| | CLEARLY SHOW LENGTH AND WIDTH OF TYPICAL |
| | SHOWER AND HANDICAP SHOWER STALL.COMPLY |
| | W/FACBC SECS.4.21-4.21.8. |
| | |
| | THE ACCESSIBLE (HANDICAP)UNITS SHALL BE |
| | DISPERSED AMONG THE VARIOUS CLASSES AND |
| | FLOORS PER FACBC SEC.9.1.4.(1). |
| | |
| | SHOW TYPICAL CLEARANCE FOR WATER CLOSETS |
| | PER SPC SEC.403.4.& FACBC FIG.28 FOR |
| | ACCESSIBLE UNITS. |
| | |
| | ALL PUBLIC AND COMMON USE AREA TOILET |
| | ROOMS SHALL BE FULLY ACCESSIBLE PER |
| | FACBC SEC.4.1.3.(11),9.1. |
| | |
| | SUBMIT DETAILS ON SCUPPERS (LXW) AND |
| | CALCULATIONS FOR OVERFLOW (SECONDARY) |
| | DRAINAGE.COMPLY W/SBC SEC.1517.6.4., |
| | 1517.6.4.2.,1517.6.4.3.,SPC 1108.2.2, |
| | 1108.3. |
| | |
| | SECONDARY DRAIN SYSTEM SHALL COMPLY W/ |
| | SPC 1109.2,1109.3,AND APPENDIX"A".(THE |
| | OVERFLOW SYSTEM IS INADEQUATE PER NOTED |
| | CODE SECS.) |
| | |
| | LENGTH OF GRAB BARS BEHIND WATER CLOSETS |
| | SHALL COMPLY W/FACBC SEC.4.16.4. |
| | |
| | SHT.A9.4-DETAIL #12-H.C.WATER TO BE 18" |
| | FROM WALL.FACBC FIG.30. |
| | |
| | FLOORS AND WALLS IN COMMON/PUBLIC AREA |
| | RESTROOMS SHALL COMPLY W/SBC SEC.1204.2 |
| | |
| | DRINKING FOUNTAIN ON ROOF SHALL COMPLY |
| | W/FACBC SEC.4.1.3.(10)(A). |
| | |
| | SHT.M-4-SHOWS OVERFLOW FROM COOLING |
| | TOWERS AND CHEMICAL FEEDER TO SANITARY. |
| | PH OF EFFLUENT SHALL COMPLY W/SPC SEC. |
| | 701.5.(DATA FROM MANUF.REQD.INDICATING |
| | PH LEVELOF EFFLUENT AT POINT OF |
| | DISCHARGE.) |
| | |
| | PANS AND PAN DRAINS ARE REQD.FOR THE |
| | WATER HEATERS PER COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.507.8.1. |
| | |
| | SUBMIT U.L.ASSEMBLY NUMBERS FOR FIRE |
| | SAFING DETAILS PER COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.104.2.4.(SEE SHT.P-400) |
| | |
| | SUBMIT COMPLETE ISOMETRIC FOR THE U/G |
| | SANITARY SYSTEM DRAWN IN COMPLIANCE W/ |
| | ASSE STANDARD #1043 FOR SOVENT SYSTEM. |
| | |
| | SHOW LOCATION OF WATER TREARMENT SYSTEM |
| | ON PLAN. |
| | |
| | SEE PLBG.REVIEW STEP#2 FOR CONTINUATION |
| | OF COMMENTS.1/19/00. |