| Plan Review Notes For Permit 99121640 |
| Permit Number |
99121640 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CORRECTED BY REVISION****************** | | | | | | 1)SHT LS1.1 NOTE XL EMERGENCY SERVICES | | | NOTE D- DUCT SMOKE DETECTOR ALSO REQUIRE | | | FOR UNITS LESS THAN 2000 CFM BUT SERVING | | | AREAS USED FOR EGRESS-PER 1997 SMC 406.2 | | | ALSO REFERENCED SHT M-0.02 NOTE 16 | | | 2)SHT M-2.1 OUTSIDE AIR INTAKE DUCT (24X | | | 8) REQUIRES FIRE DAMPER @ RATED WALL | | | PENETRATION 2 PLACES | | | 3)SHT M-2.1 OUTSIDE AIR INTO TRANSFORMER | | | VAULT PENETRATES RATED (4 HR) WALL, | | | REQUIRES FIRE DAMPER OF EQUAL RATING | | | EXHAUST FAN PENETRATES SAME 4 HR WALL | | | PROVIDE DETAIL ON OPENING PROTECTIVES | | | PER 1997 SMC 610.6 | | | 4) SHT M-2.2 EXHAUST FANS TERMINATE IN | | | TOILET COMPARTMENT, PROVIDE EXHAUST AIR | | | TO ROOM WITH SHOWER/ TUB | | | 5) EXHAUST DUCTS PENETRATING RATED WALL | | | REQUIRE PROTECTION PER 1997 SMC 610.1 | | | PROVIDE DETAILS | | | 6)SHT M-2.5 PROVIDE DETAIL FOR LEVEL 1 | | | MACHINE ROOM COMPLIANCE FOR MECHANICAL | | | ROOM WITH CHILLER | | | 7)SHT M-4.1 OVERFLOW PROTECTION REQUIRED | | | PER 1997 SMC 304.8.6 | | | 8) PROVIDE DETAIL ON TERMINATION OF COND | | | ENSATE DRAIN LINE AND DRAINLINE SIZES | | | AND VENTING OF STACK |
|