Plan Review Notes
Plan Review Notes For Permit 99121632
Permit Number 99121632
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST RE-
 -VIEW. NOT ALL NOTES WERE ADDRESSED.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE,PLEASE
 LIST THE REQ`D BATH(S) CIRCUIT(S) PER
 210-11-C-3. #12, 20A.
  
 3)NOTE: PLEASE SEE 384-15. PANELS ARE
 NOT PERMITTED TO HAVE MORETHAN 42 SPACES
  
 4)NOTE: PLEASE SEE 210-8-A-6.ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO GFI/
 GFI PROTECTED. PLEASE SHOW AND PLEASE
 SHOW ON KITCHEN OPT PLAN ALSO.
  
 5)NOTE: PLEASE SEE 210-52H FOR OUTLET
 REQ`D IN MASTER BEDROOM HALLWAY.
  
 6)NOTE: PLEASE SHOW THE MAIN DISCONNECT
 ON THE PLAN AS IT IS SHOWN ON THE RISER
 DIAGRAM. 215-5
  
 7)NOTE: PLEASE SUBMIT SUBMIT CLARIFICAT-
 ION ON THE "DOUBLE TUB" WRIITEN ON RISER
 AND PANEL SCHEDULE??
  
  
 PLEASE MAKE THE ABOVE CHANGES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372