| Plan Review Notes For Permit 99121632 |
| Permit Number |
99121632 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SHOW THE AIC RATING OF | | | EQUIPMENT MAINS. MAINS ARE TO BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. AS REQ` | | | -D BY ARTS: 110-9/110-10/215-5 OF THE | | | NEC. PLEASE SHOW ON PLANS/ | | | | | | 2)NOTE:PLEASE CORRECT THE OPTIONAL | | | KITCHEN PLAN. | | | | | | 3)NOTE: RISER DIAGRAM SHOW MAIN DISC. | | | PLEASE DRAW ON PLANS NEXT TO METERCAN. | | | | | | 4)NOTE: SHOW THE OTHER GROUND AS BEING | | | BLDG.STEEL. | | | | | | 5)NOTE:AS REQ`D BY 210-52H NEED TO HAVE | | | OUTLET IN THE MASTER BEDROOM HALL.10` | | | OR MORE. | | | | | | 6)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. | | | | | | 7)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. AS REQ`D BY 210-8-A-6 | | | | | | | | | PLEASE HAVE ALL THE ABOVE INFORMATION | | | SUBMITTED FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|