2001-02-14 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS DRAWINGS STILL SHOW THE WRONG
 MEAN ROOF HEIGHT. THIS IS A TWO STORY
 BUILDING. THE MEAN ROOF HEIGHT IS +/-
 22'-0". REVISE AS REQUIRED.
 2-SBC 1997 DOESN'T USE "WALL HEIGHT". IT
 USES THE MEAN ROOF HEIGHT OF THE
 BUILDING. REVISE ENGINEERED ROOF
 TRUSSES AS REQUIRED.
 3-CHECK IF CONNECTORS SPECIFIED WILL BE
 ADEQUATE TO SUPPORT THE LOADS AS
 CALCULATED ON THE REVISED ENGINEERED
 TRUSSES PRIOR TO SUBMITTAL TO THIS
 OFFICE.
 4-UNABLE TO IDENTIFY ENGINEER.
 -ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND NUMBER ON EACH
 SHEET AS REQUIRED BY CHAPTER 471 OF
 FLORIDA STATUTES.