Plan Review Notes
Plan Review Notes For Permit 99121626
Permit Number 99121626
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A8". PROVIDE ELEVATION
 CERTIFICATION.
 2-PROVIDE SIGNED AND SEALED SURVEY.
 3-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS CALCULATED BY THE
 ENGINEER. SEC. 1606 SBC 1997.
 4-RESUBMIT ENERGY CALCULATIONS. ALL
 SIGNATURES TO BE ORIGINAL. NOT COPIES.
 SEC. 103.0 FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION,1997 ED
 5-PROVIDE PRODUCT APPROVAL FOR:
 -FLAT ROOF ROOF SYSTEM.
 -ENTRY DOOR. DOOR SHOWN ON PLAN IS AN
 INSWING DOOR, WHILE PRODUCT APPROVAL
 IS FOR AN OUTSWING DOOR. RE-SUBMIT.
 -GARAGE DOORS DRAWINGS ARE NOT LEGIBLE.
 ALSO, CHECK DESIGN PRESSURES AS
 CALCULATED BY THE ENGINEER.
 -PROVIDE COPIES OF TESTS DONE TO THE
 SLIDINGGLASS DOORS AS PER ASTM E-330
 STANDARDS. SECTION 1706 SBC 1997.
 6-SEE COMMENTS ON PLANS.