| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
E |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE GROUPING OF MAINS | | | PER 230-72 NOT MET. | | | | | | 2)NOTE: PLEASE NOTE SHUNT TRIP(S) | | | SHOWN AS A MAIN DISCONNECT FOR 6E. | | | PLEASE SEE 230-76 AND 230-79 | | | | | | 3)NOTE: PLEASE NOTE ELECTRICAL ROOM(S) | | | LAYOUTS DO NOT CORRELATE WITH HOW IT | | | IS ACTUALLY INSATLLED IN THE FIELD. | | | | | | 4)NOTE: PLEASE NOTE MAIN 1&2 "W" ON | | | FIRST FLOOR AND NOT GROUPED WITH OTHERS | | | ALSO DOES NOT MEET THE REQ`MENTS FOR | | | FIRE DEPT. | | | | | | 5)NOTE: PLEASE SUBMIT OCP FOR FIRE PUMPS | | | AND ASSC EQUIPMENT. PLEASE SEE 695-4/ | | | 695-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|