| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
B |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | METAL FRAMING SHOP DRAWINGS, | | | CALCULATIONS BY THOMAS KELLEHER PE. | | | THE CALCULATIONS CITE ASCE 7-93.THE | | | 1997 SBCCI INVOKED THE ASCE 7-95. | | | PLEASE REVISE AS NECESSARY. | | | | | | PROVIDE A METAL FRAMING DETAIL FOR THE | | | CANOPY THAT THE " TITAN ROOFING" PANELS | | | WILL BE ATTACHED TO. | | | | | | THE FIRE PROTECTION SYSTEM FOR THE | | | CANOPY IS A COLUMN DESIGN.HOW ARE THE | | | HORIZONTAL STRUCTURAL MEMBERS PROTECTED? |
|