| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
B |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2002-05-14 00:00:00 | REVISIONS SUBMITTED 5/7/02 | | | SHEET A801 DATED 5/2/02.SECTION | | | 6/A801WHAT IS THE 1 1/2" ACCENT PANEL | | | MADE OF? HOW IS IT ATTACHED? | | | | | | WHERE IN THE STRUCTURAL DRAWINGS IS THE | | | FRAMING DETAIL FOUND? | | | | | | SSK 19THE NEW 7'-4" HEIGHT DOES NOT | | | COMPLY WITH THE 98" HEIGHT REQUIRED BY | | | THE FACBC SEC 4.6.5.IF IT IS NOT ON | | | THE SITE ACCESSIBLE ROUTE PROVIDE | | | SIGNAGE AS APPLICABLE. | | | | | | SSK 26-28SPECIFY THE TYPE OF WELDS TO | | | BE USED IN ACCORDANCE WITH GOOD | | | ENGINEERING PRACTICE.IF THE | | | CONNECTIONS ARE TO BE DELEGATED, | | | PROVIDE THE APPROPRIATE INFORMATION ON | | | THE DRAWING.SEE 61G15-31.009 | | | | | | SSK 27 PLAN VIEW SHOWS THE FRONT OF THE | | | CANOPY AS BEING STRAIGHT. THE | | | ARCHITECTURAL PLANS DEPICT IT AS BEING | | | CURVED.HOW IS THIS ACCOMPLISHED? |
|