| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
FIRE |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | THIS PLAN REVIEW STOP IS FOR THE | | | PRODUCT APPROVAL DATA THAT WAS SUBMITTED | | | FOR THE HOOD EXHAUST DUCT SCRUBBER UNIT | | | PROPOSED FOR ONE OF THE RETAIL SPACES. | | | PLEASE BE ADVISED THAT IF THIS UNIT IS | | | ACCEPTABLE TO CITY OFFICIALS, A SEPARATE | | | FIRE SUPPRESSION SYSTEM WILL BE REQUIRED | | | PER NFPA 96. ALSO NO DOWNGRADES OF THE | | | EXHAUST DUCT BEYOND THE SCRUBBER UNIT | | | WILL BE PERMITTED. ALSO APPROVAL IS | | | DIFFICULT TO GIVE AT THIS TIME BECAUSE | | | PLANS HAVE NOT BEEN RECEIVED OR REVIEWED | | | FOR THE TENANT SPACE HOOD,DUCT,AND | | | EXTINGUISHING SYSTEM WHICH WOULD WORK | | | IN CONJUNCTION WITH THE PROPSED | | | SCRUBBER UNIT. THE EXHAUST DUCT | | | TERMINATIONS MUST COMPLY WITH THE | | | REQUIREMENTS OF NFPA 96 AS WELL AS THE | | | REST OF THE INSTALLATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|