| Date |
Text |
| 2002-05-10 00:00:00 | REVISIONS SUBMITTED 5/1/02 |
| | SHEET A110 REVISIONS NUMBERED 1-8.THE |
| | PERMIT PLANS HAVE REV 1, SOME OF THE |
| | REVISONS ARE DATED TWO YEARS AGO, WHY |
| | ARE THEY JUST NOW BEING PROVIDED TO THE |
| | CITY FOR REVIEW? |
| | |
| | PROVIDE DETAILS FOR THE BUILT IN BAR |
| | SHOWN INCLUDING HC ACCESIBILITY |
| | REQUIREMENTS. |
| | |
| | THE PLANS HAVE REFERENCE SECTIONS TO |
| | A802.THE PERMIT PLANS DO NOT SHOW |
| | SECTION DETAILS NUMBERED THAT HIGH, |
| | THEYSTOP AT DETAIL 6, THESE PLANS SHOW |
| | 17. |
| | |
| | SHEET A111.PROVIDE A CONSTRUCTION |
| | DETAIL FOR THE SUSPENDED CEILING. |
| | REVISIONS SHOWN 1-6, PERMIT PLANS 0. |
| | |
| | SHEET A120 REVISIONS 1-6, PERMIT PLAN 0. |
| | THE HANDRAILS FOR THE STAIRS FROM THE |
| | POOL DECK TO THE CLUBHOUSE DO NOT |
| | COMPLY WITH THE 30" REACH RANGE OF SBC |
| | 1007.5.7.THE STAIRS AT THE FOUNTAIN |
| | AREA REQUIRE HANDRAILS ON BOTH SIDES |
| | AND THE RANGE OF REACH REQUIREMENTS OF |
| | SBC 1007.5.2ANDSBC 1007.5.7. |
| | |
| | SHEET A201 REV 1-8, PERMIT SET 1-4. |
| | PROVIDE STRUCTURAL DETAILS FOR THE |
| | CANOPY.THIS WAS REQUESTED ON MY |
| | CHECKLIST DATED 4/18/02 DENYING THOSE |
| | REVISIONS. |
| | |
| | WHAT PERMITTED PLAN DID THE THRESHOLD |
| | INSPECTOR USE TO INSPECT THIS |
| | STRUCTURAL WORK? |
| | |
| | SHEET A323 REVISIONS 1-3, PERMIT SET 1. |
| | PROVIDE A CONSTRUCTION DETAIL FOR THE |
| | ADDED MASONRY VEHICLE BARRIER WALL |
| | INCLUDING CALCULATIONS DEMONSTRATING |
| | COMPLIANCE WITH THE LOADS PRESCRIBED IN |
| | SBC 1608.2.3. |
| | |
| | SHEET A404 REVISIONS 1-4, PERMIT SET 0. |
| | PROVIDE A DETAIL FOR CONSTRUCTION OF |
| | THEADDED VAULT. |
| | |
| | SHEET A406 REVISIONS 1-5, PERMIT SET 0. |
| | PROVIDE DETAILS FOR THE GALVANIZED |
| | SHUTTER.WHAT IS IT FOR?THE 4" HIGH |
| | CURBS AT THE PATIO SLIDING DOORS DO NOT |
| | COMPLY WITH THE FAIR HOUSING ACT.SEE |
| | PART 2, CHAPTER 4, PAGE 4.11 OF THE FHA |
| | DESIGN MANUAL. |
| | |
| | SHEET A421 REVISIONS 1-3, PERMIT SET 0. |
| | PROVIDE A DETAIL OF WHAT THE ADDED |
| | WALKWAY WILL BE MADE OF. |
| | |
| | SHEET A425 REVISIONS 1-3, PERMIT SET 0. |
| | SECTION DETAILS REFERENCED AS"XX/804" |
| | ARE ABSENT FROM THE PERMIT PLANS. |
| | |
| | SHEET E1.06, PROVIDE INFORMATION FOR THE |
| | METHOD OF OPENING PROTECTIVE FOR THE |
| | ADDED EXHAUST FAN.SEE SBC TABLE 600. |