| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) MORE INFORMATION REQUIRED FOR THE | | | FIREFIGHTERS SMOKE CONTROL STATION. THE | | | PLANS DO NOT INDICATE WHAT WILL BE | | | FEATURED ON THE PANEL. PLEASE REFER TO | | | NFPA 92A, SECTION 3-4.3.4 REGARDING | | | MINIMUM REQUIREMENTS. | | | 2) NO TESTING EQUIPMENT NOTED ON | | | DRAWINGS. PLEASE SEE NFPA 92A, SECTION | | | 4-3.2. THIS EQUIPMENT SHALL BE NOTED | | | ON THE PLANS TO ASSIST IN TESTING THESE | | | LIFE SAFETY SYSTEMS. | | | 3) TYPE AND DURATION OF SMOKE BOMBS | | | TO BE USED NOT IDENTIFIED. NO CRITERIA | | | NOTED ON WHAT IS EXPECTED DURING TESTING | | | WITH SMOKE BOMBS. |
|