| 2002-03-06 00:00:00 | |
| | MECHANICAL PERMIT 00120524 |
| | |
| | PLEASE PROVIDE MANUFACTURER SUBMITTAL |
| | DATA FOR DRYERS BEING INSTALLED IN |
| | UNITS THAT THE IN-LINE FAN HAS BEEN |
| | DELETED.EXHASUT DUCT EXCEEDS 25 FT |
| | MAXIMUM AS PER 1997 SMC 509.3. |
| | |
| | REVISIONS APPROVED WITH THE EXCEPTION |
| | OF"PROPOSED KITCHEN HOOD".TERMINATION |
| | FOR GREASE DUCT SHALL COMPLY WITH NFPA |
| | 96 AND 1997 SMC CHAPTER 5.TERMINATION |
| | OF EXHAUST SHALL BE LOCATED 10 FT FROM |
| | ANY ADJACENT BUILDING, PARKING AREA, |
| | ADJACENT PROPERTY LINE, WINDOW, DOOR OR |
| | AIR INTAKE.ADDITIONAL PLANS & PERMITS |
| | REQUIRED FOR HOOD (GREASE DUCT & MAKEUP |
| | AIR), FIRE SUPRESSION, AND WALKIN |
| | COOLERS/FREEZERS. |
| | |
| | PROVIDE MANUFACTURER SUBMITTAL DATA |
| | WITH PLANS & PERMIT APPLICATION.PLEASE |
| | NOTE, THERE SHALL BE NO DOWNGRADING |
| | OTHER PARTS OF THE EXHAUST SYSTEM DUE |
| | TO THE INSTALLATION OF THE "ECOLO AIR" |
| | SYSTEM AS PER NFPA 96 6-3.FIRE |
| | SUPRESSION SYSTEM REQUIRED AS PER NFPA |
| | 96 6-3.1. |
| | |
| | PLEASE NOTE 1 SET OF REVISIONS SUBMITTED |
| | MECHANICAL SHEETS M104, M106, & M108, |
| | ARE DIFFERENT.REVISION 4 IS DATED JUL |
| | 20, 2001 AND PLAN SHEETS DIFFER.THE |
| | OTHER SET OF PLANS SUBMITTED THE |
| | AFOREMENTIONED PLAN SHEETS ARE DATED |
| | JUL 20, 2001 AND ALSO INDICATE LATEST |
| | REVISON TO BE #4. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |