| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
B |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2002-07-16 00:00:00 | REVISIONS SUBMITTED 6/24/02 SHEETS | | | ADD-1 AND A801 TOGETHER WITH DORSKY | | | HODGSON LETTER/ LAWRENCE LORDI. | | | | | | UL 419 AND UL 428 ARE RECOGNIZED | | | ASSEMBLIES.UL 419 HAS FOUR POSSIBLE | | | ASSEMBLIES FOR THE DESIRED TWO HOUR | | | WALL CONSTRUCTION.WHICH IF ANY, WERE | | | USED IN THE TWENTY ONE ENCLOSURES | | | POSSIBILITIES SHOWN ON THIS SHEET? | | | WHERE WAS THE UL 428 SHAFT WALL USED? | | | | | | RESPONSES #7 AND #8 IN THE DORSKY | | | HODGSON LETTER DATED 6/18/02 SIGNED BY | | | LAWRENCE LORDI.REGARDING THE CANOPY, | | | THE HEIGHT ABOVE FINISH GRADE, | | | (SIDEWALKS) WAS NOT SHOWN. | | | | | | I HAVE INCLUDED COPIES OF TWO PAGES FROM | | | THE FAIR HOUSING ACT DESIGN MANUAL | | | WHICH CLEARLY INDICATE A FOUR INCH HIGH | | | "CURB" IS CONTRADICTORY TO THE ALLOWED | | | FOUR INCH "DROP" CONTAINED IN THAT | | | PUBLICATION. | | | | | | REVISONS #3 AND #4 ON SHEET A801 ARE | | | APPROVED. | | | | | | SHEET ADD-1 IS BEING REJECTED, FOR THE | | | ABOVE REASONS. | | | | | | THOSE WERE THE ONLY TWO PAGES IN THIS | | | SUBMITTAL. |
|