| Plan Review Notes For Permit 99121621 |
| Permit Number |
99121621 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********NOT ENOUGH INFORMATION****** | | | | | | INSUFFICIENT MECHANICAL INFORMATION TO | | | REVIEW: | | | PROVIDE DETAILS AT TIME OF SUBMITION FOR | | | BUILDING REVIEW. INCLUDE: | | | EQUIPMENT TYPES AND LOCATION | | | REFRIGERANT TYPE AND QUANTITY PER 1997 | | | SMC CHAPTER 11 | | | DUCT LAYOUT, SIZES AND SPECIFICATIONS | | | FAN SHUT DOWN PER 1997 SMC 406,NFPA90A, | | | AND 1997 SBC 412.2 | | | SMOKE CONTROL PER 1997 SBC 412.5 | | | STAIRWELL PRESSURIZATION PER 1997 SMC | | | 408 AND NFPA 92A | | | INCLUDE SEQUENCE OF OPERATION FOR SMOKE | | | CONTROL AND FAN SHUT DOWN SYSTEMS | | | SHAFT ENCLOSURE DETAILS FOR EXHAUST DUCT | | | FOR HOOD AND MAKE UP AIR LOCATION FOR | | | HOOD | | | OUTSIDE AIR CALCULATIONS AND AIR BALANCE | | | SCHEDULE PER ASHRAE 62-89 AND SMC 501.2 | | | | | | | | | NOTE:SMC=STANDARD MECHANICAL CODE | | | SBC=STANDARD BUILDING CODE | | | NFPA=NATIONAL FIRE PROTECTION ASSOCIA- | | | TION |
|