Plan Review Notes
Plan Review Notes For Permit 99121619
Permit Number 99121619
Review Stop R
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00TRUSSES CHECKLIST:
 1-WHERE IS THE ENGINEERING FOR THE
 PARALAM BEAM?
 2-DESIGN CRITERIA SHALL BE SPECIFIC:
 SBCCI IS NOT THE BUILDING CODE. IT IS
 THE ENTITY WHO PUBLISHES IT. THE
 ACTUAL BUILDING CODE IS THE SBC 1997
 STANDARD BUILDING CODE, 1997).
 3-THERE SHALL BE ONLY ONE MEAN ROOF
 HEIGHT FOR ENTIRE BUILDING. REVISE
 ENGINEERED TRUSS DRAWINGS AS REQUIRED.
  
  
  
  
  
  
  
  
 NOTES:
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -PLEASE DON'T FORGET THAT THE ENGINEER
 OF RECORD NEEDS TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE.