Date Text
2001-01-08 00:00:00DENIED
  
 1)DETAIL OF FLOOR TRUSS,SHOWN ON SHEET
 A-5,ENTERING AND TERMINATING IN MASONRY
 WALL HAS NO PROVISION FOR FIRE CUT.1997
 SBC SEC.2305.4.
  
 2)FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3)SURVEY INDICATES RIGHT SIDE OF
 STRUCTURE IS LOCATED ON PROPERTY LINE.
 TABLE 600 OF 1997 SBC DOES NOT ALLOW ANY
 OPENINGS IN A WALL LOCATED ON ZERO LOT
 LINES. THE PLANS SHOW A SLIDING GLASS
 DOOR AND 2 WINDOWS IN THIS WALL.OPTIONAL
 WALL & GATE, A/C EQUIPMENT & PAD, PAD
 OUTSIDE SGD AND CONC. FOOTER FOR COLUMN
 ARE ALL ENCROACHING ON ADJACENT LOT.
 PLEASE CORRECT.
  
 4)SUBMIT REVISED STORM PANEL KEY PLAN
 AND SCHEDULE THAT CORRESPONDS TO THE
 OPTIONS THAT WILL BE USED.
  
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR EXTERIOR
 OUTSWING STEEL DOOR WITH SIDELITES AS
 INDICATED ON PLANS. PRODUCT APPROVALS
 ARE REQUIRED FOR SPECIFIC PRODUCT THAT
 WILL BE INSTALLED.
  
 6)THE VALUES LISTED IN THE WIND PRESSURE
 SCHEDULE ON SHEET A-4A DO NOT AGREE WITH
 THE PRESSURES LISTED ON THE DRAWING FOR
 WINDOWS J,S & T. PLEASE CORRECT.
  
 7)ADDITIONAL IMPACT FEES ARE OWED TO THE
 COUNTY FOR THE ADDITIONAL 268 SQFT UNDER
 A/C WHEN LOFT OPTION IS ADDED AS
 INDICATED ON PRINTS.
  
 8)SPECIFICATIONS FOR GARAGE DOOR
 INCLUDED WITH PRODUCT APPROVAL INDICATE
 A NEGATIVE DESIGN PRESSURE OF -33PSF FOR
 16'X 7' DOOR, WIND LOADS SHOWN ON PLANS
 SHEET A-4A LISTS NEG. PRESSURE OF -34PSF
 PLEASE CORRECT.