| Plan Review Notes For Permit 99121599 |
| Permit Number |
99121599 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE:PLEASE REVISE SHEET E1.1 TO | | | REFLECT WIRE SIZE FOR SITE LIGHTING AS | | | REQ`D ON SHEET E5.1. | | | | | | 2)NOTE:AS REQ`D BY ARTS;250-81/250-94 | | | OF THE NEC. THE BONDING JUMPER/GROUNDING | | | ELECTRODE CONDUCTOR GOING TO COLD WATER | | | PIPEIS REQ`D BY 250-81 TO BE SIZED | | | FROM 250-94. PLEASE CORRECT. | | | | | | 3)NOTE: THERE IS TO BE NO EQUIUPMENT | | | GROUNDING CONDUCTOR INSTALLLED UNTIL | | | AFTER FIRST MEANS OF DISCONNECT. | | | | | | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR RE- | | | -VIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|