Plan Review Notes
Plan Review Notes For Permit 99121526
Permit Number 99121526
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00******************PROVISO***************
 THE PLANS HAVE BEEN REVIEWED FOR
 COMPLIANCE W/THE STANDARD PLUMBING CODE
 WITH THE FOLLOWING PROVISOS:
  
 1)INTERCEPTOR VENT SHALL BE TAKEN OFF
 INTERCEPTOR NOT MORE THAN 45 DEGREES
 FROM THE VERTICAL PER SPC SEC.906.2.1.
 UNLESS BASE OF VENT IS WASHED BY A
 FIXTURE.SEE SHT.P-3.
  
 2)SHT.P-5-MIN.AIR GAP FOR CONDENSATE
 DRAIN DISCHARGE TO LEADER SHALL COMPLY
 W/SPC SEC.806.
  
 3)SHT.P-5-EWH SHOWN ON PLATFORM.HEATER
 SHALL BE READILY ACCESSIBLE PER SPC
 SEC.501.7.SUPPLY SHIP'S LADDER AND PLAT-
 FORM OR RELOCATE EWH TO FLOOR.
  
 4)CONTACT R.COMPO AT CITY OF WPB
 WASTEWATER TREATMENT PLANT FOR APPROVAL
 OF SAND/OIL INTERCEPTOR.
 PHONE #561-835-7423
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.