| Plan Review Notes For Permit 99121526 |
| Permit Number |
99121526 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | THE PLANS HAVE BEEN REVIEWED FOR | | | COMPLIANCE W/THE STANDARD PLUMBING CODE | | | WITH THE FOLLOWING PROVISOS: | | | | | | 1)INTERCEPTOR VENT SHALL BE TAKEN OFF | | | INTERCEPTOR NOT MORE THAN 45 DEGREES | | | FROM THE VERTICAL PER SPC SEC.906.2.1. | | | UNLESS BASE OF VENT IS WASHED BY A | | | FIXTURE.SEE SHT.P-3. | | | | | | 2)SHT.P-5-MIN.AIR GAP FOR CONDENSATE | | | DRAIN DISCHARGE TO LEADER SHALL COMPLY | | | W/SPC SEC.806. | | | | | | 3)SHT.P-5-EWH SHOWN ON PLATFORM.HEATER | | | SHALL BE READILY ACCESSIBLE PER SPC | | | SEC.501.7.SUPPLY SHIP'S LADDER AND PLAT- | | | FORM OR RELOCATE EWH TO FLOOR. | | | | | | 4)CONTACT R.COMPO AT CITY OF WPB | | | WASTEWATER TREATMENT PLANT FOR APPROVAL | | | OF SAND/OIL INTERCEPTOR. | | | PHONE #561-835-7423 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|