| 2001-02-05 00:00:00 | ************DENIED********************** | | | 1. SMOKE FIRE DAMPERS INDICATED ON | | | ELECTREICAL PLAN ARE NOT CLEARLY | | | INDICATED ON MECHANICAL DRAWING. 1997 | | | SMC 610.6 REQUIRES LOCATION AND | | | INSTALLATION DETAILS TO BE CLEARLY | | | INDICATED ON THE PLAN BY THE DESIGNER. | | | 2. EXHAUST FAN # 16 SHOWS AIR EXHAUSTING | | | INTO THE RETURN AIR PLENUM AREA. 1997 | | | SMC 501.4 REQUIRES AN INDEPENDANT | | | SYSTEM FOR EXHAUST AND THAT THE AIR | | | SHALL NOT BE RECIRCULATED. RUN EXHAUST | | | FROM THIS SPACE OUT OF THE BUILDING. |
|