2001-02-05 00:00:00************DENIED**********************
 1. SMOKE FIRE DAMPERS INDICATED ON
 ELECTREICAL PLAN ARE NOT CLEARLY
 INDICATED ON MECHANICAL DRAWING. 1997
 SMC 610.6 REQUIRES LOCATION AND
 INSTALLATION DETAILS TO BE CLEARLY
 INDICATED ON THE PLAN BY THE DESIGNER.
 2. EXHAUST FAN # 16 SHOWS AIR EXHAUSTING
 INTO THE RETURN AIR PLENUM AREA. 1997
 SMC 501.4 REQUIRES AN INDEPENDANT
 SYSTEM FOR EXHAUST AND THAT THE AIR
 SHALL NOT BE RECIRCULATED. RUN EXHAUST
 FROM THIS SPACE OUT OF THE BUILDING.