| 2001-01-08 00:00:00 | 1)SUBMIT CIVIL DRAWINGS FOR REVIEW. |
| | PERMITS MAY BE REQD.FROM THE DEPT.OF |
| | ENVIRONMENTAL PROTECTION & PALM BEACH |
| | COUNTY HEALTH DEPT. FOR THE WATER AND |
| | SEWER INSTALLATIONS.COUNTYWIDE AMEND- |
| | MENTS TO SPC SECS.101.4.7,104.2.1. |
| | |
| | 2)ROOM 133-DOOR CANNOT SWING INTO THE |
| | CLEAR FLOOR SPACE FOR THE URINAL PER |
| | FACBC SEC.4.22.2. |
| | |
| | 3)SHT.P-1-CONNECTION OF CONDENSATE |
| | DRAINS TO STORM SYSTEM SHALL BE BY |
| | INDIRECT CONNECTIONS.SUBMIT DETAIL OF |
| | CONNECTION TO DOWNSPOUT.SPC SEC.807.2. |
| | |
| | 4)WATER HEATERS SHALL BE READILY ACCESS- |
| | IBLE.(CAR STEREO INSTALLATION).IF ACCESS |
| | TO THE CONCRETE DECK REQUIRES THE USE |
| | OF A PORTABLE LADDER,THE HEATER IS NOT |
| | READILY ACCESSIBLE AS DEFINED BY THE |
| | SPC.SUBMIT ADDITIONAL INFO FOR THIS |
| | INSTALLATION.SEE SHT.P-5 ALSO.SPC 501.7. |
| | |
| | 5)A VALVE IS REQD.ON THE HOT WATER |
| | BRANCH LINES PER SPC SEC.610.4.2. |
| | (SEE AUTO INSTALLATION AND EMPLOYEE |
| | AREAS.) |
| | |
| | 6)SHT.P-6-CIRCUIT AND LOOP SYSTEM SHALL |
| | COMPLY W/SPC SEC.914.1.(MAX.OF 4 F.U.'S |
| | PERMITTED ON VENT DOWNSTREAM OF FIRST |
| | FIXTURE CONNECTION.) |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |