2001-01-08 00:00:001)SUBMIT CIVIL DRAWINGS FOR REVIEW.
 PERMITS MAY BE REQD.FROM THE DEPT.OF
 ENVIRONMENTAL PROTECTION & PALM BEACH
 COUNTY HEALTH DEPT. FOR THE WATER AND
 SEWER INSTALLATIONS.COUNTYWIDE AMEND-
 MENTS TO SPC SECS.101.4.7,104.2.1.
  
 2)ROOM 133-DOOR CANNOT SWING INTO THE
 CLEAR FLOOR SPACE FOR THE URINAL PER
 FACBC SEC.4.22.2.
  
 3)SHT.P-1-CONNECTION OF CONDENSATE
 DRAINS TO STORM SYSTEM SHALL BE BY
 INDIRECT CONNECTIONS.SUBMIT DETAIL OF
 CONNECTION TO DOWNSPOUT.SPC SEC.807.2.
  
 4)WATER HEATERS SHALL BE READILY ACCESS-
 IBLE.(CAR STEREO INSTALLATION).IF ACCESS
 TO THE CONCRETE DECK REQUIRES THE USE
 OF A PORTABLE LADDER,THE HEATER IS NOT
 READILY ACCESSIBLE AS DEFINED BY THE
 SPC.SUBMIT ADDITIONAL INFO FOR THIS
 INSTALLATION.SEE SHT.P-5 ALSO.SPC 501.7.
  
 5)A VALVE IS REQD.ON THE HOT WATER
 BRANCH LINES PER SPC SEC.610.4.2.
 (SEE AUTO INSTALLATION AND EMPLOYEE
 AREAS.)
  
 6)SHT.P-6-CIRCUIT AND LOOP SYSTEM SHALL
 COMPLY W/SPC SEC.914.1.(MAX.OF 4 F.U.'S
 PERMITTED ON VENT DOWNSTREAM OF FIRST
 FIXTURE CONNECTION.)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.