| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS TO BE PLACED ON |
| | BUILDING IN ACCORDANCE WITH CITY |
| | ORDINANCE. |
| | 2) TRAVEL DISTANCE OF 250 FEET SHWON ON |
| | PLANS. SINCE THE BUILDING IS A MIXED |
| | OCCUPANCY THE MOST STRINGENT TRAVEL |
| | DISTANCE SHALL APPLY. MAXIMUM TRAVEL |
| | DISTANCE PERMITTED IS 150 FEET WITH |
| | SPRINKLER PROTECTION. |
| | 3) INTERIOR FINISHES SHALL BE CLASS A |
| | OR B ON CEILING AND WALLS. AGAIN THE |
| | BUILDING IS A MIXED OCCUPANCY, THE |
| | MOST STRINGENT INTERIOR FINISH |
| | REQUIREMENTS ARE TO BE APPLIED. |
| | 4) PLEASE PROVIDE MORE DETAILS ON FIRE |
| | SHUTTERS. |
| | 5) PLEASE PROVIDE MORE DETAILS ON |
| | EMERGENCY GENERATOR. SINCE GENERATOR |
| | HAD A FUEL SUB-TANK, THE REQUIREMENTS |
| | OF NFPA 30 ARE TO APPLY. ROOM IS TO BE |
| | A MINIMUM OF TWO HOUR FIRE RATED. |
| | 6) ELEVATOR TO COMPLY WITH ANSI A17.1. |
| | 7) NO FIRE HYDRANTS SHOWN. WHERE ARE |
| | THE FIRE HYDRANTS LOCATED FOR THE STORE. |
| | ADDITIONAL FIRE HYDRANTS MAY BE NEEDED |
| | ON SITE. |
| | 8) HANDRAILS AND GUARDS TO COMPLY WITH |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION. |
| | 9) NO FIRE LANE SHOWN ON PLANS. |
| | 10) ANY CHANGES IN ELEVATIONS GREATER |
| | THAN 21 INCHES SHALL BE BY RAMPS. STEPS |
| | WHEN INSTALLED SHALL HAVE A MINIMUM OF |
| | THREE STEPS AT 7 INCHES EACH. |
| | 11) A KNOX-BOX IS TO BE PROVIDED FOR |
| | FIRE RESCUE ACCESS. |