Plan Review Notes
Plan Review Notes For Permit 99121526
Permit Number 99121526
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001) BUILDING ADDRESS TO BE PLACED ON
 BUILDING IN ACCORDANCE WITH CITY
 ORDINANCE.
 2) TRAVEL DISTANCE OF 250 FEET SHWON ON
 PLANS. SINCE THE BUILDING IS A MIXED
 OCCUPANCY THE MOST STRINGENT TRAVEL
 DISTANCE SHALL APPLY. MAXIMUM TRAVEL
 DISTANCE PERMITTED IS 150 FEET WITH
 SPRINKLER PROTECTION.
 3) INTERIOR FINISHES SHALL BE CLASS A
 OR B ON CEILING AND WALLS. AGAIN THE
 BUILDING IS A MIXED OCCUPANCY, THE
 MOST STRINGENT INTERIOR FINISH
 REQUIREMENTS ARE TO BE APPLIED.
 4) PLEASE PROVIDE MORE DETAILS ON FIRE
 SHUTTERS.
 5) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR. SINCE GENERATOR
 HAD A FUEL SUB-TANK, THE REQUIREMENTS
 OF NFPA 30 ARE TO APPLY. ROOM IS TO BE
 A MINIMUM OF TWO HOUR FIRE RATED.
 6) ELEVATOR TO COMPLY WITH ANSI A17.1.
 7) NO FIRE HYDRANTS SHOWN. WHERE ARE
 THE FIRE HYDRANTS LOCATED FOR THE STORE.
 ADDITIONAL FIRE HYDRANTS MAY BE NEEDED
 ON SITE.
 8) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 9) NO FIRE LANE SHOWN ON PLANS.
 10) ANY CHANGES IN ELEVATIONS GREATER
 THAN 21 INCHES SHALL BE BY RAMPS. STEPS
 WHEN INSTALLED SHALL HAVE A MINIMUM OF
 THREE STEPS AT 7 INCHES EACH.
 11) A KNOX-BOX IS TO BE PROVIDED FOR
 FIRE RESCUE ACCESS.