Plan Review Notes
Plan Review Notes For Permit 99121526
Permit Number 99121526
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS
 MAY BE REQD.FROM THE DEPT.OF ENVIRON.
 PROTECTION & PALM BEACH COUNTY HEALTH
 DEPT.FOR WATER AND SEWER INSTALLATIONS.
 COUNTYWIDE AMENDMENTS TO SPC SECS.
 101.4.7,104.2.1.
  
 SHT.A-2-NOTE #6-MEASUREMENT OF GRAB BARS
 A.F.F.SHALL BE TO THE CENTER OF THE BAR,
 NOT TO THE TOP.FACBC SEC.4.16.4 & FIGURE
 #29 & 30.
  
 SINK IN EMPLOYEE LOUNGE SHALL BE ACCESS-
 IBLE PER FACBC SECS.4.24.1.-4.24.7.
  
 A LAVATORY IS REQD.IN THE TOILET STALL
 IN ROOM #132 AND THE SIZE OF THE STALL
 SHALL COMPLY W/FACBC SEC.4.17.3.THE DOOR
 CANNOT SWING INTO THE CLEAR FLOOR SPACE
 REQD.FOR ANY FIXTURE.FACBC SEC.4.22.2.
  
 URINAL IN TOILET ROOM IN WAREHOUSE AND
 IN RETAIL AREA SHALL COMPLY W/FACBC SEC.
 4.18.MAX.17" AFF TO THE RIM & 30"X 48"
 CLEAR FLOOR SPACE.
  
 THE NUMBER OF EMPLOYEES PER SHIFT IN THE
 WAREHOUSE AREA SHALL BE SUBSTANTIATED BY
 OWNER PER SPC TABLE 407.
  
 THE MINIMUM NUMBER OF REQUIRED SANITARY
 FACILITIES SHALL COMPLY W/TABLE 407 OF
 SPC BASED ON THE TOTAL NUMBER OF PERSONS
 NOT 50% MALE, 50% FEMALE.ADDITIONAL
 FIXTURES ARE REQD.
  
 SUBMIT PIPING ISOMETRIC FOR "SIZZRDOK"&
 ELEVATOR SUMP AREAS.COMPLY W/SPC 717.2,
 717.9,717.11.
  
 SUBMIT INSTALLATION DETAILS ON PNEUMATIC
 TUBE SYSTEM.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 SUBMIT DETAILS FOR SECONDARY (EMERGENCY)
 DRAINAGE.COMPLY W/SPC SEC.1109.1-1109.3.
 AND APPENDIX "A" OF SPC.
  
 SHT.P-1-CONNECTION OF CONDENSATE DRAINS
 TO STORM SYSTEM SHALL BE BY INDIRECT
 CONNECTIONS PER SPC 807.2.
  
 WATER HEATERS SHALL BE READILY ACCESS-
 IBLE PER FACBC SEC.501.7.SUPPLY FIXED
 LADDER ORRELOCATE EWH TO FLOOR.
  
 SHT.P-4-SHOWS A 4" LINE DRAINING INTO A
 2" LINE.SPC SEC.307.5.
  
 HOT WATER SYSTEM SHALL BE VALVED PER SPC
 SECS.610.4.1,610.4.2.
  
 SHT.P-4.-OVER 4 FIXTURES CONNECTED TO
 1/2"HOT WATER.COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 MECHANICAL SHOCK ABSORBERS REQUIRE
 ACCESS PER 607.8.3.
  
 SHT.P-6-LOCATION OF DRINKING FOUNTAINS
 ON SANITARY RISER DOESN'T MATCH FLOOR
 PLAN.
  
 TWO-WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET OF THE OIL INTERCEPTOR PER
 SPC SEC.710.4.DELETE REFERENCE TO SFBC.
  
 SHOW WATER CONNECTION TO EWH ON P-6,
 GROUND FLOOR SALES AREA.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR.
 CAPACITY SHALL BE APPROVED BY CITY OF
 WPB UTILITIES.CONTACT R.COMPO AT (561)-
 835-7423 FOR APPROVAL.
  
 SUBMIT ENERGY CALCULATIONS FOR REVIEW.
 103.0,103.1.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT (561)659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLAN REVIEW.