| 2001-01-08 00:00:00 | SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS |
| | MAY BE REQD.FROM THE DEPT.OF ENVIRON. |
| | PROTECTION & PALM BEACH COUNTY HEALTH |
| | DEPT.FOR WATER AND SEWER INSTALLATIONS. |
| | COUNTYWIDE AMENDMENTS TO SPC SECS. |
| | 101.4.7,104.2.1. |
| | |
| | SHT.A-2-NOTE #6-MEASUREMENT OF GRAB BARS |
| | A.F.F.SHALL BE TO THE CENTER OF THE BAR, |
| | NOT TO THE TOP.FACBC SEC.4.16.4 & FIGURE |
| | #29 & 30. |
| | |
| | SINK IN EMPLOYEE LOUNGE SHALL BE ACCESS- |
| | IBLE PER FACBC SECS.4.24.1.-4.24.7. |
| | |
| | A LAVATORY IS REQD.IN THE TOILET STALL |
| | IN ROOM #132 AND THE SIZE OF THE STALL |
| | SHALL COMPLY W/FACBC SEC.4.17.3.THE DOOR |
| | CANNOT SWING INTO THE CLEAR FLOOR SPACE |
| | REQD.FOR ANY FIXTURE.FACBC SEC.4.22.2. |
| | |
| | URINAL IN TOILET ROOM IN WAREHOUSE AND |
| | IN RETAIL AREA SHALL COMPLY W/FACBC SEC. |
| | 4.18.MAX.17" AFF TO THE RIM & 30"X 48" |
| | CLEAR FLOOR SPACE. |
| | |
| | THE NUMBER OF EMPLOYEES PER SHIFT IN THE |
| | WAREHOUSE AREA SHALL BE SUBSTANTIATED BY |
| | OWNER PER SPC TABLE 407. |
| | |
| | THE MINIMUM NUMBER OF REQUIRED SANITARY |
| | FACILITIES SHALL COMPLY W/TABLE 407 OF |
| | SPC BASED ON THE TOTAL NUMBER OF PERSONS |
| | NOT 50% MALE, 50% FEMALE.ADDITIONAL |
| | FIXTURES ARE REQD. |
| | |
| | SUBMIT PIPING ISOMETRIC FOR "SIZZRDOK"& |
| | ELEVATOR SUMP AREAS.COMPLY W/SPC 717.2, |
| | 717.9,717.11. |
| | |
| | SUBMIT INSTALLATION DETAILS ON PNEUMATIC |
| | TUBE SYSTEM.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | SUBMIT DETAILS FOR SECONDARY (EMERGENCY) |
| | DRAINAGE.COMPLY W/SPC SEC.1109.1-1109.3. |
| | AND APPENDIX "A" OF SPC. |
| | |
| | SHT.P-1-CONNECTION OF CONDENSATE DRAINS |
| | TO STORM SYSTEM SHALL BE BY INDIRECT |
| | CONNECTIONS PER SPC 807.2. |
| | |
| | WATER HEATERS SHALL BE READILY ACCESS- |
| | IBLE PER FACBC SEC.501.7.SUPPLY FIXED |
| | LADDER ORRELOCATE EWH TO FLOOR. |
| | |
| | SHT.P-4-SHOWS A 4" LINE DRAINING INTO A |
| | 2" LINE.SPC SEC.307.5. |
| | |
| | HOT WATER SYSTEM SHALL BE VALVED PER SPC |
| | SECS.610.4.1,610.4.2. |
| | |
| | SHT.P-4.-OVER 4 FIXTURES CONNECTED TO |
| | 1/2"HOT WATER.COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.607.7. |
| | |
| | MECHANICAL SHOCK ABSORBERS REQUIRE |
| | ACCESS PER 607.8.3. |
| | |
| | SHT.P-6-LOCATION OF DRINKING FOUNTAINS |
| | ON SANITARY RISER DOESN'T MATCH FLOOR |
| | PLAN. |
| | |
| | TWO-WAY CLEANOUTS ARE REQD.ON THE INLET |
| | AND OUTLET OF THE OIL INTERCEPTOR PER |
| | SPC SEC.710.4.DELETE REFERENCE TO SFBC. |
| | |
| | SHOW WATER CONNECTION TO EWH ON P-6, |
| | GROUND FLOOR SALES AREA. |
| | |
| | SUBMIT DETAIL OF GREASE INTERCEPTOR. |
| | CAPACITY SHALL BE APPROVED BY CITY OF |
| | WPB UTILITIES.CONTACT R.COMPO AT (561)- |
| | 835-7423 FOR APPROVAL. |
| | |
| | SUBMIT ENERGY CALCULATIONS FOR REVIEW. |
| | 103.0,103.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS I CAN BE |
| | REACHED AT (561)659-8096,EXT.8377. |
| | TIMOTHY LARGE,PLUMBING PLAN REVIEW. |