| 2001-01-08 00:00:00 | ***********DENIED*********************** |
| | |
| | 1.1997 SMC 406.2 REQUIRES FAN SHUT DOWN |
| | BY DUCT SMOKE DETECTOR FOR UNITS WITH A |
| | CAPACITY OF 2,000 CFM OR LESS BUT |
| | SERVING AREAS USED FOR EGRESS. RTU# 10 |
| | W/ 600 CFM SERVICES AN AREA USED FOR |
| | EGRESS AND SHALL BE PROVIDED WITH FAN |
| | SHUT DOWN BY DUCT SMOKE DETECTOR. |
| | 2.RTU'S # 9 AND #10 HAVE NO OUTSIDE AIR |
| | SHOWN. THESE UNITS APPEAR TO SERVE AREAS |
| | WITH OCCUPANCY AND ARE SEPARATE FROM |
| | COMMON AREAS OF THE BUILDING. OUTSIDE |
| | AIR PER ASHRAE 62-89 SHALL BE PROVIDED |
| | 3.EF'S #5, #6, AND #7 ARE CONTROLLED BY |
| | THE CO2 SENSOR AND WOULD SHUT DOWN WHEN |
| | THE CO2 LEVEL IS BELOW 1000PPM. THIS |
| | WOULD PLACE THE PRESSURE IN THE BUILDING |
| | IN CONFLICT WITH THE REQUIREMENTS OF |
| | 1997 SMC 501.2 REQUIRING PRESSURE EQUIL- |
| | IZATION PROVIDING FOR THE REMOVAL OF |
| | EXCESS AIR SUPPLIED. AIR BALANCE |
| | SCHEDULE AS SHOWN INDICATES AN AIR |
| | BALANCE IN ACCORDANCE WITH THE ABOVE |
| | SECTION. THE REMOVAL OF THESE FANS FROM |
| | THE BALANCE SCHEDULE IS NOT COMPLIANCE |
| | WITH THIS SECTION OF THE CODE |
| | |
| | NOTE: |
| | RTU'S SHOW A 0-25% MOTOR OPERATED |
| | OUTSIDE AIR DAMPER FOR EACH UNIT. THE |
| | QUANTITY OF OUTSIDE AIR PROVIDED IS THE |
| | MINIMUM REQUIRED BY ASHRAE 62-89 AND |
| | SHALL NOT BE REDUCED WHILE THE BUILDING |
| | IS OCCUPIED. SHOW SEQUENCE OF OPERATION |
| | FOR MOTORIZED DAMPERS INDICATING |
| | PROPOSED OPERATION. |
| | NOTE: |
| | RETURN AIR PLENUM AREAS (AS INDICATED ON |
| | PLAN AS ABOVE CEILING AREAS) ARE TO BE |
| | CONSTRUCTED ENTIRELY OF NONCOMBUSTIBLE |
| | MATERIAL PER 1997 SMC 609.1. |
| | NOTE: |
| | PROVIDE INFORMATION ON MAKE UP AIR FOR |
| | WAREHOUSE EXHAUST FANS (SOURCE/LOCATION) |
| | 1997 SMC 501.2 |