Plan Review Notes
Plan Review Notes For Permit 99121526
Permit Number 99121526
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:PLEASE SEE PP13 ON E-12. ALL
 CONTINUOUS LOADS TO BE SHOWN AT 125%
  
 2)NOTE: PLEASE SEE LOADS SHOWN ON PP14
 EM2,UPS PANEL. PLEASE SEE THAT ALL
 LOADS DO NOT COERRELATE. LOADS SHOWN ON
 UPS PANEL TOTAL AT 3KVA PER PHASE AND
 CONNECTED SHOWN HIGHER ON PANEL SCHEDULE
 PLEASE SEE PP14 CONNECTED SHOWN AT 28.42
 AND CONNECTED ON PANEL AT 29.42 AND
 TOTAL AT BOTTOM SHOWN AT 25.42.PLEASE
 CORRELATE THE ABOVE LOADS.
  
 3)NOTE: PLEASE SEE LP1 CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125%. CONTINUOUS
 LOADSON OTHER PANELS SHOWN AT 125%???
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASECALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372