| Plan Review Notes For Permit 99121526 |
| Permit Number |
99121526 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE:PLEASE SEE PP13 ON E-12. ALL | | | CONTINUOUS LOADS TO BE SHOWN AT 125% | | | | | | 2)NOTE: PLEASE SEE LOADS SHOWN ON PP14 | | | EM2,UPS PANEL. PLEASE SEE THAT ALL | | | LOADS DO NOT COERRELATE. LOADS SHOWN ON | | | UPS PANEL TOTAL AT 3KVA PER PHASE AND | | | CONNECTED SHOWN HIGHER ON PANEL SCHEDULE | | | PLEASE SEE PP14 CONNECTED SHOWN AT 28.42 | | | AND CONNECTED ON PANEL AT 29.42 AND | | | TOTAL AT BOTTOM SHOWN AT 25.42.PLEASE | | | CORRELATE THE ABOVE LOADS. | | | | | | 3)NOTE: PLEASE SEE LP1 CONTINUOUS LOADS | | | NEED TO BE SHOWN AT 125%. CONTINUOUS | | | LOADSON OTHER PANELS SHOWN AT 125%??? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASECALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|