Plan Review Notes
Plan Review Notes For Permit 99121526
Permit Number 99121526
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT CIVIL DRAWINGS FOR REVIEW.PERMITS
 MAY BE REQD.FROM DEPT.OF ENVIRON.PROT.
 AGENCY & PALM BEACH COUNTY HEALTH DEPT.
 FOR WATER AND SANITARY INSTALLATIONS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
 104.2.1..
  
 SINK IN EMPLOYEE LOUNGE SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 SHT.A2.4-HEIGHT OF URINAL TO RIM SHALL
 BE A MAX.OF 17" TO RIM PER FACBC SEC.
 4.18.2.
  
 HEIGHT OF ACCESSIBLE WATER CLOSET SHALL
 BE 17"-19"AFF PER FACBC SEC.4.16.3.&
 FLUSH CONTROLS SHALL BE LOCATED ON THE
 WIDE SIDE OF THE WATER CLOSET MAX.44"AFF
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(B).(WHERE MORE THAN 1 IS
 PROVIDED ON A FLOOR,AT LEAST 50% SHALL
 COMPLY W/FACBC SEC.4.15)
  
 SHOW REQD.WHEELCHAIR TURNING SPACE IN
 TOILET ROOMS AND RESTROOMS PER FACBC
 SEC.4.2.3.
  
 ACCESSIBLE URINAL SHALL BE LOCATED ON AN
 ACCESSIBLE ROUTE PER FACBC SEC.4.1.2(2).
 (SEE MEN'S R.R.#138.)SHOW REQD.30"X 48"
 CLEAR FLOOR ACCESS FOR URINAL ON PLAN.
  
 A LAVATORY IS REQD.IN THE STALL IN THE
 MEN'S TOILET ROOM #132 PER FACBC SEC.
 4.1.2 (6),4.1.3.(11),4.17.3,4.22.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.PROVIDE FIXED LADDER
 OR RELOCATE EWH TO FLOOR.
  
 PLANS REFER TO SCUPPERS.SUBMIT DETAILS,
 DIMENSIONS,LOCATIONS ON PLANS.COMPLY W/
 SPC APPENDIX "A".
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLETS AT THE OIL INTERCEPTOR PER
 SPC 710.4.
  
 INDICATE SLOPE OF STORM DRAINAGE PIPING
 ON PLANS.COMPLY W/SPC TABLE 1108.2.
  
 SUBMIT DETAIL OF GREASE TRAP FOR REVIEW.
 APPROVAL REQD.FROM CITY OF WEST PALM
 BEACH REGIONAL WASTEWATER TREATMENT
 PLANT.CONTACT R.COMPO AT 835-7423.SUBMIT
 COPY OF APPROVAL.
  
 SUBMIT PIPING DETAILS(ISOMETRICS)FOR ALL
 COMPRESSED AIR PIPING,PUMP DISCHARGE
 FROM TRUCK LIFT,ELEVATOR SUMP.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 SHT.P-5-DELETE NOTE REFERRING S.F.B.C.
 DADE COUNTY EDITION.COUNTYWIDE AMENDMENT
 TO SPC SEC.101.1,101.2.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SECS.610.4.1,610.4.2.
  
 SUBMIT COMPLETE ISOMETRIC FOR OILY WASTE
 AND GREASY WASTE SYSTEM.COUNTYWIDE AMEND
 MENTS TO SPC SEC.104.2.1.
  
 SUBMIT DOCUMENTATION OF OCCUPANT CONTENT
 PER SHIFT IN WAREHOUSE FOR COMPLIANCE W/
 TABLE 407 OF SPC FOR PLBG.FIXTURES.