| Plan Review Notes For Permit 99121526 |
| Permit Number |
99121526 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************DENIED******************* | | | | | | 1.1997 SMC 610.6 REQUIRES THE SPECIFIC | | | LOCATION AND INSTALLATION DETAILS OF EA | | | FIRE DOOR, FIRE DAMPER, CEILING DAMPER, | | | ETC. TO BE SHOWN AND PROPERLY IDENTIFIED | | | ON BUILDING PLANS BY THE DESIGNER | | | 2.AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 1997 SMC 406 WITH NOTIFICA- | | | TION PER 1996 NFPA 4-4.4.2 (TIED TO BLDG | | | FIRE ALARM SYSTEM) | | | 4.PROVIDE CALCULATIONS SHOWING | | | COMPLIANCE WITH REQUIREMENTS OF 1997 SBC | | | 411.4.2 (CONTINUOUS VENTILATION REQUIRED | | | - NOT TO BE INTERVAL SWITCHED) | | | 5.PROVIDE INFORMATION ON PURPOSE OF CO2 | | | SENSOR SHOWN ON M-1 LEGEND |
|