Plan Review Notes
Plan Review Notes For Permit 99121526
Permit Number 99121526
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************DENIED*******************
  
 1.1997 SMC 610.6 REQUIRES THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF EA
 FIRE DOOR, FIRE DAMPER, CEILING DAMPER,
 ETC. TO BE SHOWN AND PROPERLY IDENTIFIED
 ON BUILDING PLANS BY THE DESIGNER
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1997 SMC 406 WITH NOTIFICA-
 TION PER 1996 NFPA 4-4.4.2 (TIED TO BLDG
 FIRE ALARM SYSTEM)
 4.PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH REQUIREMENTS OF 1997 SBC
 411.4.2 (CONTINUOUS VENTILATION REQUIRED
 - NOT TO BE INTERVAL SWITCHED)
 5.PROVIDE INFORMATION ON PURPOSE OF CO2
 SENSOR SHOWN ON M-1 LEGEND