| Plan Review Notes For Permit 99121519 |
| Permit Number |
99121519 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | JOB SPECS.15400-3-SEC.2.06-RELIEF DRAIN | | | SHALL BE PIPED TO EXTERIOR PER COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.507.6 (3). | | | | | | SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/ | | | SPC SEC.407.1.3(ADD'L.PLBG.FIXTURES | | | ARE REQD.) | | | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407. | | | | | | LOCATION OF BACKFLOW PREVENTION DEVICE | | | SHALL BE DETERMINED BY CITY OF WPB | | | UTILITIES.CALL 659-8000. | | | | | | DESIGN OF CIRCUIT AND LOOP VENTING | | | SYSTEM SHALL COMPLY W/SPC SEC.914.1. | | | | | | SHT.P-21-DELETE FUNNEL DRAIN AND INSTALL | | | FLOOR SINK PER SPC SEC.807.1.3. | | | | | | HOSE BIBBS SHALL BE VALVED PER SPC SEC. | | | 610.4.1. | | | | | | SUBMITDATA FOR PH OF EFFLUENT FROM | | | PHOTO SINK PH SHALL BE BETWEEN 5.0-10.0. | | | COMPLY W/SPC SEC.301.3. | | | | | | INDICATE ON PLANS HOW SILVER AND | | | CHEMICALS FROM RECOVERY UNIT WILL BE | | | DISPOSED. | | | | | | CLEARLY SHOW WATER SUPPLY SOURCE FOR | | | IRRIG.SYSTEM.A WATER USE PERMIT MAY BE | | | REQD.PER F.S.373.219. | | | | | | PHOTO SINK NOT SHOWN ON WATER RISER, | | | | | | SHT.A1.3 SHOWS VTR'S WITHIN 10' OF ROOF | | | EXHAUST.COMPLY W/SPC 905.5. |
|