Plan Review Notes
Plan Review Notes For Permit 99121519
Permit Number 99121519
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00JOB SPECS.15400-3-SEC.2.06-RELIEF DRAIN
 SHALL BE PIPED TO EXTERIOR PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.507.6 (3).
  
 SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/
 SPC SEC.407.1.3(ADD'L.PLBG.FIXTURES
 ARE REQD.)
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.
  
 LOCATION OF BACKFLOW PREVENTION DEVICE
 SHALL BE DETERMINED BY CITY OF WPB
 UTILITIES.CALL 659-8000.
  
 DESIGN OF CIRCUIT AND LOOP VENTING
 SYSTEM SHALL COMPLY W/SPC SEC.914.1.
  
 SHT.P-21-DELETE FUNNEL DRAIN AND INSTALL
 FLOOR SINK PER SPC SEC.807.1.3.
  
 HOSE BIBBS SHALL BE VALVED PER SPC SEC.
 610.4.1.
  
 SUBMITDATA FOR PH OF EFFLUENT FROM
 PHOTO SINK PH SHALL BE BETWEEN 5.0-10.0.
 COMPLY W/SPC SEC.301.3.
  
 INDICATE ON PLANS HOW SILVER AND
 CHEMICALS FROM RECOVERY UNIT WILL BE
 DISPOSED.
  
 CLEARLY SHOW WATER SUPPLY SOURCE FOR
 IRRIG.SYSTEM.A WATER USE PERMIT MAY BE
 REQD.PER F.S.373.219.
  
 PHOTO SINK NOT SHOWN ON WATER RISER,
  
 SHT.A1.3 SHOWS VTR'S WITHIN 10' OF ROOF
 EXHAUST.COMPLY W/SPC 905.5.