| Plan Review Notes For Permit 99121519 |
| Permit Number |
99121519 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED******************** | | | 1)ERV-2 SHOWS EXHAUST DUCT TIED TO O/A | | | OF UNIT AND FRESH AIR DUCT TIED TO EX- | | | HAUST CONNECTION OF UNIT | | | 2)COSTGARD CONDENSATE DRAIN NOT APPROVE | | | NO PRODUCT APPROVAL, PROVIDE DETAIL | | | ON CONDENSATE | | | 3)NFPA 90A 4-4.4.2 REQUIRES NOTIFICA- | | | TION TO BUILDING AS WELL AS TROUBLE TO | | | PANEL | | | 4)PROVIDE OUTSIDE AIR CALCS PER ASHRAE | | | 62-89 | | | 5)AREAS WITH 300CFM OR GREATER REQUIRES | | | RETURN FROM AREA | | | 6)PROVIDE DETAIL ON ERV FOR 15' SEPARA- | | | TION OF EXHAUST AIR FROM OUTSIDE AIR IN- | | | TAKE |
|