2001-01-08 00:00:00*************DENIED********************
 1)ERV-2 SHOWS EXHAUST DUCT TIED TO O/A
 OF UNIT AND FRESH AIR DUCT TIED TO EX-
 HAUST CONNECTION OF UNIT
 2)COSTGARD CONDENSATE DRAIN NOT APPROVE
 NO PRODUCT APPROVAL, PROVIDE DETAIL
 ON CONDENSATE
 3)NFPA 90A 4-4.4.2 REQUIRES NOTIFICA-
 TION TO BUILDING AS WELL AS TROUBLE TO
 PANEL
 4)PROVIDE OUTSIDE AIR CALCS PER ASHRAE
 62-89
 5)AREAS WITH 300CFM OR GREATER REQUIRES
 RETURN FROM AREA
 6)PROVIDE DETAIL ON ERV FOR 15' SEPARA-
 TION OF EXHAUST AIR FROM OUTSIDE AIR IN-
 TAKE