| 2001-01-08 00:00:00 | ************PROVISO******************** |
| | |
| | 1)NOTE:NEED TO SUBMIT AIC RATING OF |
| | EQUIPMENT MAINS/PANELS. AIC RATING IS |
| | FIGURED FROM FAULT CURRENT CALCULATIONS. |
| | THIS IS REQ`D BY THE FOLLOWING ARTS; |
| | 110-9/230-65/215-5 |
| | |
| | 2)NOTE: ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE LABELED GFI/GFI |
| | PROTECTED AS REQ`D BY 210-8-A-6/215-5 |
| | |
| | 3)NOTE: PLEASE CHECK OUTLET SPACING |
| | FOR REQ`D OUTLETS SERVING COUNTERSPACE. |
| | REQ`D PER 210-52-C-1 |
| | |
| | 4)NOTE:CHECK ALL WALL SPACES EXCEEDING |
| | 2`. OUTLET SPACING TO MEET NEC PER ART; |
| | 210-52 |
| | |
| | 5)NOTE;SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D |
| | BY 1993/1996 NFPA-72 2-2.1.1.1.IN NEW |
| | DWELLING UNITS. |
| | |
| | 6)NOTE:PLEASE SHOW CONDUCTOR SIZE FOR |
| | RISER. ALSO PLEASE SHOW ON RISER DIAGRAM |
| | GROUNDING ELECTRODE CONDUCTOR GOING TO |
| | GRND.ROD AND BLDG.STEEL. AS REQ`D BY THE |
| | FOLLOWING ARTS:215-5/250-81 |
| | |
| | 7)NOTE:PLEASE SHOW ON PANEL SCHEDULE THE |
| | REQ`D DEDICATED BATH(S) CIRCUT(S) PER |
| | ART:210-52D/215-5 |
| | |
| | 8)NOTE:AIR CONDITIONING LOAD TABLE SHOW |
| | SECOND A/C`S AS N/A??? YET LOADYOU |
| | SHOW TWO A/C`S ON LOAD CALCULATION. |
| | PLEASE CORRELATE. 215-5 |
| | |
| | |
| | PLEASE HAVE ALL THE ABOVE INFORMATION |
| | SUBMITTED FOR REVIEW AND APPROVAL |
| | BEFORE FIRST ROUGH ELECTRICAL INSPECTION |
| | IS CALLED IN. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8373 |