Plan Review Notes
Plan Review Notes For Permit 99121470
Permit Number 99121470
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************PROVISO********************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS/PANELS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 THIS IS REQ`D BY THE FOLLOWING ARTS;
 110-9/230-65/215-5
  
 2)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE LABELED GFI/GFI
 PROTECTED AS REQ`D BY 210-8-A-6/215-5
  
 3)NOTE: PLEASE CHECK OUTLET SPACING
 FOR REQ`D OUTLETS SERVING COUNTERSPACE.
 REQ`D PER 210-52-C-1
  
 4)NOTE:CHECK ALL WALL SPACES EXCEEDING
 2`. OUTLET SPACING TO MEET NEC PER ART;
 210-52
  
 5)NOTE;SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D
 BY 1993/1996 NFPA-72 2-2.1.1.1.IN NEW
 DWELLING UNITS.
  
 6)NOTE:PLEASE SHOW CONDUCTOR SIZE FOR
 RISER. ALSO PLEASE SHOW ON RISER DIAGRAM
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 GRND.ROD AND BLDG.STEEL. AS REQ`D BY THE
 FOLLOWING ARTS:215-5/250-81
  
 7)NOTE:PLEASE SHOW ON PANEL SCHEDULE THE
 REQ`D DEDICATED BATH(S) CIRCUT(S) PER
 ART:210-52D/215-5
  
 8)NOTE:AIR CONDITIONING LOAD TABLE SHOW
 SECOND A/C`S AS N/A??? YET LOADYOU
 SHOW TWO A/C`S ON LOAD CALCULATION.
 PLEASE CORRELATE. 215-5
  
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8373