Plan Review Notes
Plan Review Notes For Permit 99121467
Permit Number 99121467
Review Stop R
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00TRUSSES
  
 ***************DENIED*******************
  
 1)TRUSS DRAWINGS NOT REVIEWED BY
 DESIGNER OF RECORD.TRUSS LAYOUT MUST BE
 SIGNED AND DATED BY DESIGNER OF
 STRUCTURE AND SIGNED SEALED AND DATED BY
 TRUSS ENGINEER.
  
 2)PROVIDE TRUSS SHOP DRAWINGS SIGNED
 (WET SIGNATURE),SEALED AND DATED,EACH
 PAGE.
  
  
 3)DESIGN CRITERIA USED FOR TRUSS
 DRAWINGS IS ASCE7-93,THE DESIGN STANDARD
 FOR CURRENT CODE (97 SBC) IS ASCE7-95.
 PLEASE PROVIDE UPDATED DESIGN CRITERIA.
  
 4)ROOF LOADS SPECIFIED ON ARCHITECTURAL
 PLANS DO NOT COINCIDE WITH THE LOADS ON
 TRUSS LAYOUT. PLEASE REVISE.
  
 5)ENGINEERED ROOF TRUSS DRAWINGS NOTE #2
 GIVES HOUSE DIMENSIONS AS 45'X 24'.THESE
 DO NOT CORRESPOND WITH THE DIMENSIONS ON
 ARCHITECTURAL DRAWINGS.PLEASE REVISE.
  
 6)SPECIFY TRUSS TO TRUSS ANCHORS TO BE
 USED.
  
  
  
 IF YOU HAVE ANY QUESTIONS CALL ROBERT
 MCDOUGAL AT (561) 659-8096 EXT.8202