| 2001-01-08 00:00:00 | ************* PROVISO ****************** |
| | |
| | 1)NOTE: PLEASE CHECK AND CORRECT OUTLET |
| | SPACING ALONG KITCHEN COUNTERTS. AS PER |
| | 210-52-C-1 |
| | |
| | 2)NOTE:AS PER 210-8-A-6 ALL OUTLETS |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI/GFI PROTECTED. PLEASE LABEL. |
| | |
| | 3)NOTE: AS REQ`D BY 1993/1996 NFPA-72 |
| | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | IN NEW DWELLINGS. |
| | |
| | 4)NOTE: OUTLET SPACING TO MEET 210-52 |
| | 2`6`12` RULE. THIS INCLUDE KITCHEN. |
| | |
| | 5)NOTE: AS REQ`D BY 215-5 PLEASE SHOW |
| | WIRE SIZES IN RISER. |
| | |
| | 6)NOTE:PLEASE SHOW GROUND ROD AND BLDG. |
| | STEEL AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM.AS REQ`D PER 250-81/215-5 |
| | |
| | 7)NOTE:PLEASE LIST DEDICATED BATH(S) |
| | CIRCUT(S) ON PANEL SCHEDULE.20AMP #12 |
| | AS REQ`D BY NEC ART;210-52D |
| | |
| | 8)NOTE:PLEASE RE-DO LOAD CALCULATION |
| | TO CORRELATE. A/C LOAD TABLE SHOWS ONLY |
| | ONE A/C?? BUT PANEL LOAD CALC. INDICATES |
| | 20,000 KW AS LOAD?? PLEASE CORRECT. |
| | |
| | 9)NOTE: AS REQ`D BY NEC ARTS:110-9/215-5 |
| | 230-65. NEED TO SUBMIT AIC RATING OF |
| | MAINS/PANEL. AIC RATING IS FIGURED FROM |
| | FAULT CURRENT CALCULATIONS. |
| | |
| | PLEASE HAVE ALL THE ABOVE INFORMATION |
| | SUBMITTED FOR REVIEW AND APPROVAL |
| | BEFORE FIRST ROUGH ELECTRICAL INSPECTION |
| | IS CALLED IN. IF THERE ARE ANY QUESTIONS |