2001-01-08 00:00:00************* PROVISO ******************
  
 1)NOTE: PLEASE CHECK AND CORRECT OUTLET
 SPACING ALONG KITCHEN COUNTERTS. AS PER
 210-52-C-1
  
 2)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. PLEASE LABEL.
  
 3)NOTE: AS REQ`D BY 1993/1996 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS.
  
 4)NOTE: OUTLET SPACING TO MEET 210-52
 2`6`12` RULE. THIS INCLUDE KITCHEN.
  
 5)NOTE: AS REQ`D BY 215-5 PLEASE SHOW
 WIRE SIZES IN RISER.
  
 6)NOTE:PLEASE SHOW GROUND ROD AND BLDG.
 STEEL AS PART OF THE GROUNDING ELECTRODE
 SYSTEM.AS REQ`D PER 250-81/215-5
  
 7)NOTE:PLEASE LIST DEDICATED BATH(S)
 CIRCUT(S) ON PANEL SCHEDULE.20AMP #12
 AS REQ`D BY NEC ART;210-52D
  
 8)NOTE:PLEASE RE-DO LOAD CALCULATION
 TO CORRELATE. A/C LOAD TABLE SHOWS ONLY
 ONE A/C?? BUT PANEL LOAD CALC. INDICATES
 20,000 KW AS LOAD?? PLEASE CORRECT.
  
 9)NOTE: AS REQ`D BY NEC ARTS:110-9/215-5
 230-65. NEED TO SUBMIT AIC RATING OF
 MAINS/PANEL. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT.8372