2001-04-23 00:00:00*************BUILDING UNSAT*************
  
 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO RECEIVING A C.O.
  
 2) THE TYPICAL EXTERIOR CEILING DETAIL
 ON SHEETS A-1 & A-1B IS FOR VERTICLE
 APPLICATION. SECTION 2504.2.2 OF THE
 1997 SBC REFERS TO ASTM C 1603, WHICH
 REQUIRES 1 3/4" PENETRATION INTO
 HORIZONTAL WOOD FRAMING MEMBERS FOR LATH
 ON CEILINGS. PLEASE CORRECT.
  
 3) THE MAXIMUM HEIGHT OF THE PRIVACY
 WALL INDICATED ON SHEETS A-1 & A-1B IS
 6'. PLEASE CORRECT.
  
 4) THE PRESSURES LISTED IN THE WINDOW
 PRESSURE SCHEDULE ON SHEETS A-4A & A-4B
 FOR (J,S,&T) DO NOT CORRESPOND WITH
 THOSE LISTED ON THE ELEVATION DRAWINGS
 ON THE SAME SHEETS. PLEASE CORRECT.
  
 5) SECTION 104.2.1 OF THE CITY OF W.P.B.
 AMENDMENTS TO THE 97 SBC REQUIRES
 INFORMATION TO BE SPECIFIC AND STATES
 THAT THE TECHINCAL CODES SHALL NOT BE
 CITED. ON SHEETS A-3A & A-8A THE STAIR
 DETAILS STATE THAT STAIRS ARE TO BE
 CONSTRUCTED IN ACCORDANCE W/SEC. 1007 OF
 1997 SBC. PLEASE PROVIDE DETAILS OF
 HANDRAILS AND GUARDRAILS, INCLUDING
 SPACING OF INTERMEDIATE RAILS, ETC.
  
 6) PER SEC.1007.3 OF 1997 SBC THE SUM OF
 2 RISERS AND 1 TREAD IS TO BE NOT LESS
 THAN 24" NOR MORE THAN 25". THE
 DIMENSIONS GIVEN ON SHEETS A-3A & A-8A,
 DO NOT COMPLY. PLEASE CORRECT.
  
 7) THE ALLOWABLE WINDLOADS LISTED IN THE
 PRODUCT APPROVAL FOR A 16'X7' GARAGE
 DOOR IS EXCEEDED BY THOSE GIVEN ON SHEET
 A-4A & A-4B. PLEASE CLARIFY.
  
 THESE SAME ISSUES ARE RECURRING ON THESE
 MODELS. PLEASE MAKE THESE CORRECTIONS TO
 THE ORIGIONALS TO HELP EXPEDIATE THE
 PLAN REVIEW PROCESS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202