2001-01-08 00:00:00DENIED
  
 1)FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2)SPECIFY WHICH ELEVATION,DRAWING A-4A
 OR A-4B,WILL BE USED.
  
 3)THE VALUES LISTED IN THE WIND PRESSURE
 SCHEDULES ON SHEETS A-4A AND A-4B DO NOT
 CORRESPOND WITH THE PRESSURES LISTED ON
 THE DRAWING FOR WINDOWS J,S & T ON A-4A
 AND J,R & S ON 4B. PLEASE CORRECT.
  
 4)GARAGE DOOR SPECIFICATIONS FOR 16'X 7'
 DOOR LISTS NEGATIVE DESIGN PRESSURE OF
 -33PSF ENGINEER HAS CALCULATED NEGATIVE
 DESIGN PRESSURE OF GARAGE DOOR ON
 STRUCTURE AT -34PSF. PROVIDE PRODUCT
 APPROVAL FOR GARAGE DOOR THAT IS DESIGN-
 ED TO WITHSTAND THE PRESSURES.