| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED. | | | | | | 2)SPECIFY WHICH ELEVATION,DRAWING A-4A | | | OR A-4B,WILL BE USED. | | | | | | 3)THE VALUES LISTED IN THE WIND PRESSURE | | | SCHEDULES ON SHEETS A-4A AND A-4B DO NOT | | | CORRESPOND WITH THE PRESSURES LISTED ON | | | THE DRAWING FOR WINDOWS J,S & T ON A-4A | | | AND J,R & S ON 4B. PLEASE CORRECT. | | | | | | 4)GARAGE DOOR SPECIFICATIONS FOR 16'X 7' | | | DOOR LISTS NEGATIVE DESIGN PRESSURE OF | | | -33PSF ENGINEER HAS CALCULATED NEGATIVE | | | DESIGN PRESSURE OF GARAGE DOOR ON | | | STRUCTURE AT -34PSF. PROVIDE PRODUCT | | | APPROVAL FOR GARAGE DOOR THAT IS DESIGN- | | | ED TO WITHSTAND THE PRESSURES. |
|