| Plan Review Notes For Permit 99121448 |
| Permit Number |
99121448 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ********** REVISION REQ`ESTED ******** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM AND | | | PANEL DETAIL.?? ONE SHOWS MLO AND THE | | | OTHER MCB. PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE SHOW MAIN DISCONNECT ON | | | PLAN. MAIN NOT SHOWN NEXT TO METER?? | | | 215-5 | | | | | | 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | -ING CONDUCTOR FROM FIRST MEANS OF DISC | | | TO PANEL. SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATTION FOR | | | REVIEW BEFORE FINAL ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|