| Plan Review Notes For Permit 99121447 |
| Permit Number |
99121447 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SIZE THE PLUMBING RISER IN ITS ENTIRETY | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | ALL FIXTURES DOWMSTREAM OF WATER CLOSETS | | | SHALL BE INDIVIDUALLY VENTED PER SPC | | | 913.2.AND SHOWERS SHALL BE TRAPPED. | | | | | | SHOW DIMENSIONS OF 2ND FLR.SHOWER.(LXW) | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.409.8.2.1. | | | | | | THE LOCATION OF PLUMBING FIXTURES ON THE | | | PLUMBING RISER SHALL MATCH THE ARCH. | | | FLOOR PLAN. COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | MAIN VENT REQD.THRU ROOF.SPC SEC.904.3.1 | | | | | | BUILDING DRAIN SHALL COMPLY W/SPC SEC. | | | 714.1 & TABLE 714.1(FOOTNOTE #3.) | | | | | | CLARIFY TERMINATION POINT OF KIT.DRAIN. | | | (PLANS SHOW OPEN PIPE.) | | | | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON HORIZONTAL WET VENTS PER | | | COUNTYWIDE AMENDMENTS 911.1 |
|