Plan Review Notes
Plan Review Notes For Permit 99121367
Permit Number 99121367
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00KIT.SINKS NOT PERMITTED ON 2"VERTICAL
 COMBINATION WASTE AND VENT SYSTEM PER
 SPC SEC.911.4.
  
 SIZE ALL SECS.OF DWV SYSTEM PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 WATER CLOSETS NOT PERMITTED ON VERTICAL
 WASTE AND VENT SYSTEM PER 911.4.
  
 VENT STACK SHALL CONNECT TO HORIZ.WASTE
 PIPE PER SPC 906.2.1.BASE OF STACK SHALL
 BE WASHED.