| Plan Review Notes For Permit 99121347 |
| Permit Number |
99121347 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************UNSAT ***************** | | | | | | THIS IS MOSTLY INFORMATION PREVIOUSLY | | | ASKED FOR!!!! | | | | | | | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING OG | | | THE EQUIPMENT MAINS. MAINS MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110-9/215-5 THIS MUST BE SUBMITTED | | | ON ALL PLANS!!1 | | | | | | 2)NOTE:PLEASE SHOW ALL A/C COND. UNITS | | | AND DISC 440-11 AND REQ`D WP GFI | | | | | | 3)NOTE: MISSING OUTLETS REQ`D PER 210-52 | | | 2` 6` 12 RULE. | | | | | | 4)NOTE: ALSO, NEED TO SHOW ALL OUTLETS | | | SERVING ANY COUNTER SPACES IN KITCHEN | | | AS BEING GFI/GFI PROTECTED.210-8-A-6 | | | INCLUDING KITCHEN ISLAND/NOOK | | | | | | CHECK ORIGINAL NOTES!!YOU NEED TO SUB- | | | MIT NEW ELECTRICAL SHEETS!!! AS REQ`D BY | | | \\215-5 ONLY ELECTRICAL. PLEASE TAKE ALL | | | BUILDING NOTES OFF E-SHEETS, AND THE | | | STRUCTURE DETAILS. | | | THESE ARE NOTES THAT WERE ASKED TO BE | | | TAKEN CARE OF ON THE FIRST REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | 659-8096 EXT 8372 | | | | | | ALSO OUTLETS IN UTILITY ROOM NEED TO BE | | | GFI/GFI PROTECTED. 210-8-A-2 PLEASE SHOW |
|