Plan Review Notes
Plan Review Notes For Permit 99121347
Permit Number 99121347
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************UNSAT *****************
  
 THIS IS MOSTLY INFORMATION PREVIOUSLY
 ASKED FOR!!!!
  
  
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OG
 THE EQUIPMENT MAINS. MAINS MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110-9/215-5 THIS MUST BE SUBMITTED
 ON ALL PLANS!!1
  
 2)NOTE:PLEASE SHOW ALL A/C COND. UNITS
 AND DISC 440-11 AND REQ`D WP GFI
  
 3)NOTE: MISSING OUTLETS REQ`D PER 210-52
 2` 6` 12 RULE.
  
 4)NOTE: ALSO, NEED TO SHOW ALL OUTLETS
 SERVING ANY COUNTER SPACES IN KITCHEN
 AS BEING GFI/GFI PROTECTED.210-8-A-6
 INCLUDING KITCHEN ISLAND/NOOK
  
 CHECK ORIGINAL NOTES!!YOU NEED TO SUB-
 MIT NEW ELECTRICAL SHEETS!!! AS REQ`D BY
 \\215-5 ONLY ELECTRICAL. PLEASE TAKE ALL
 BUILDING NOTES OFF E-SHEETS, AND THE
 STRUCTURE DETAILS.
 THESE ARE NOTES THAT WERE ASKED TO BE
 TAKEN CARE OF ON THE FIRST REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 659-8096 EXT 8372
  
 ALSO OUTLETS IN UTILITY ROOM NEED TO BE
 GFI/GFI PROTECTED. 210-8-A-2 PLEASE SHOW