Plan Review Notes
Plan Review Notes For Permit 99121294
Permit Number 99121294
Review Stop ENG
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00FAILED, WITH COMMENTS:
 PERVIOUS AND IMPERVIOUS CALCULATIONS
 MUST BE SHOWN ON PAVING AND DRAINAGE
 PLAN THE TOTAL AMOUNT MUST EQUAL 100%
 OF TOTAL SITE ACRES OR S.F.
 PLEASE STATE EITHER ADDRESSES OR
 PROPERTY CONTROL NUMBERS
 STORM CHARGES WILL BE CALCULATED FROM
 THESE.
 ON WATER AND SEWER PLAN
 YOU INDICATED 5 METERS CONNECTING OFF
 THE 2" SERVICE. THIS EXCEEDS THE
 AMOUNT.
 FOR A 2" SINGLE SERVICE LINE YOU MAY HAV
 E A MAXIMUM OF 4- 5/8" BY 3/4" METERS
 OR 4- 3/4" METERS.
 PLEASE STATE THE SIZE OF PROPOSED METERS
 MOVE CLEAN-OUTS SO THAT THEY FALL JUST
 OUTSIDE OF SIDEWALK AREAS SO THAT
 IT DOES NOT POSSES A TRIPPING HAZZARD.
 ONCE REVISED TWO SETS OF PLANS MUST BE
 SUBMITTED TO PUABLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT FOR
 REVIEW. ATTENTION MANNY GONZALEZ
 PLEASE INCLUDE STORM CALCULATIONS SO
 THAT I MAY PASS THEM TO JOSE DEL RIOS
 OUR STORM WATER ENGINEER.
 1000 45TH ST, SUITE 15 WPB FL 33407
 561 659 8040 EXT. 2306
 HAVE A GREAT DAY.
 18" MIN CLR MUST BE MAINTAINED WHERE
 WATER AND SANITARY SEWER CROSSES.
 DRIVEWAYS ENTERING EACH UNIT MUST BE BUI
 LT PER CITY OF WEST PALM BEACH STANDARD
 DRIVEWAY APPROCHDETAIL.
 SEE ATTACHED. IT MAY BE REQUESTED THROUG
 H EMAIL AT [email protected].
 FL.US
 WORK PERFORMED ALONG ROW REQUIRES A
 CITY ROW PERMIT AT NO COST.
 IT CAN BE OBTAIN AT THE SAME ADDRESS
 WRITTEN ABOVE.IT MUST BE SIGN APPROVED
 BY RICHARD D. PITTMAN, CITY ENGINEER.
 HAVE A GREAT DAY IF YOU HAVE ANY QUESTIO
 NS FEEL FREE TO CONTACT MY OFFICE.
 WHEN SUBMITTING TO PUBLIC UTILITIES AGAI
 N WE JUST NEED THE PLANS MADE BY CALVIN
 GIORDANO AND ASSOCIATES. ARCHITECT PLANS
 NOT REQUIRED.