Notes
Date Text
2001-01-08 00:00:001)SUBMIT DETAILS OF REINFORCEMENT OF
 WALLS IN BATHROOMS FOR FUTURE INSTALL-
 ATION OF GRAB BARS AS REQUIRED BY THE
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 SEC.3,REQUIREMENT #6.
 NOTE:ALL BATHROOMS IN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 2)ALL BATHROOMS AND KITCHENS IN THE
 COVERED DWELLING UNIT SHALL COMPLY W/THE
 REQUIREMENTS OF THE FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205 (C)(3)(I-IV)REQ.#7(2)
 PARAGRAPH (A) OR (B).CLEAR FLOOR SPACE
 SHALL BE PROVIDED AT FIXTURES TO ALLOW A
 PERSON IN A WHEELCHAIR OR OTHER MOBILITY
 AID USE OF THE FIXTURES.THE REQD.CLEAR
 FLOOR SPACE SHALL BE SHOWN ON THE PLANS
 AND THE DESIGN OPTION (A OR B)SHALL ALSO
 BE NOTED ON THE PLANS.
  
 3)PERMITS ARE REQD.FROM P.B.COUNTY
 HEALTH DEPT.& DEPT. OF ENVIRONMENTAL
 PROTECTION FOR THE WATER SYSTEM. COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 4)WATER SERVICES SHALL BE EQUIPPED W/
 APPROVED BFP DEVICES.CONTACT CITY OF WPB
 UTILITIES FOR REQS.
  
 5)SHT.A-2-PLBG.PLAN NOTES-GENERAL
 REFERENCE TO CODE IS NOT PERMITTED PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 6)A-2-NOTE #8-INSERT"STANDARD PLUMBING
 CODE 1994 ED."INSTEAD OF NATIONAL PLBG.
 CODE.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.1.
  
 7)DRINKING FOUNTAIN FOR CABANA SHALL
 COMPLY W/FACBC SEC.4.1.3(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 8)FLOOR S AND WALLS IN CABANA SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 9)WASHERS AND DRYERS FOR DWELLING UNITS
 SHALL BE ON AN ACCESSIBLE ROUTE PER
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 (C)(3)(I)
  
 10)WATER HEATERS SHALL BE READILY
 ACCESSIBLE PER SPC SEC.501.7.SUPPLY
 SHIP'S LADDER AND PLATFORM OR RELOCATE
 EWH TO FLOOR.
  
 11)HEATER PANS SHALL BE EQUIPPED W/
 DRAINS AND COMPLY W/SPC SEC.507.8.2.
  
 12)PAN DRAINS AND EWH RELIEF VALVE SHALL
 BE PIPED TO AN APPROVED POINT OF
 DISPOSAL PER SPC SECS.507.8.3,507.8.4.
  
 13)WATER SUPPLY CONTROL FOR FIXTURES IN
 DWELLING UNITS SHALL COMPLY W/SPC SEC.
 610.3.1.
  
 14)PLUMBING FIXTURES SHALL BE OF WATER
 CONSERVATION TYPE AND COMPLY W/SPC SEC.
 406.
  
 15)WATER RISER SHOWS 1/2"LINE SUPPLYING
 A 3/4"LINE TO THE FIXTURES.MAX.OF 4
 FIXTURES SHALL BE SUPPLIED BY A 1/2"
 LINE PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.
  
 16)SUBMIT IRRIGATION PLANS FOR REVIEW.
 A WATER USE PERMIT WILL BE REQD.FROM
 SO.FLA.WATER MNGMT.AND A PERMIT FROM
 PB COUNTY HEALTH DEPT.WILL BE REQD.FOR
 THE WELL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  