| Plan Review Notes For Permit 99121294 |
| Permit Number |
99121294 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE F.A.C CHAPTER 481.221 | | | RAISED SEAL MUST BE CLEARLY VISIBLE | | | WITH NAME/NUMBER ETC. SIGNATURE MUST | | | BE DATED. | | | | | | 2)NOTE: PLEASE SHOW BLDG STEEL AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM AS REQ | | | -D BY 250-50. | | | | | | 3)NOTE: PLEASE SEE HOUSE SERVICE. AIC | | | RATING FOR MAIN DISCONNECT IS ALSO REQ`D | | | PER 215-5 AND RATED PER 110-9. | | | | | | 4)NOTE: PLEASE SEE 384-7 FOR PANEL LOCA- | | | -TION. | | | | | | 5)NOTE: PLEASE SEE F.H.A.R,24CFR 100.205 | | | FOR ALL THE REQ`MENTS OF DEVICE HEIGHTS. | | | NOT ALL NOTES SHOWN ON EM-1 COMPLY. | | | | | | 6)NOTE: PLEASE SEE LOCATION OF HWH.IN | | | BATH AND MOUNTED ABOVE. THIS MUST REMAIN | | | READILY ACCESS. FOR THE ELECTRICAL DISC- | | | -ONNECT. | | | | | | 7)NOTE: ALSO PLEASE NOTE GROUNDING ELEC- | | | -TRODE CONDUCTOR TO BLDG STEEL AS PER | | | 250-50. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|