Plan Review Notes
Plan Review Notes For Permit 99121294
Permit Number 99121294
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE F.A.C CHAPTER 481.221
 RAISED SEAL MUST BE CLEARLY VISIBLE
 WITH NAME/NUMBER ETC. SIGNATURE MUST
 BE DATED.
  
 2)NOTE: PLEASE SHOW BLDG STEEL AS PART
 OF THE GROUNDING ELECTRODE SYSTEM AS REQ
 -D BY 250-50.
  
 3)NOTE: PLEASE SEE HOUSE SERVICE. AIC
 RATING FOR MAIN DISCONNECT IS ALSO REQ`D
 PER 215-5 AND RATED PER 110-9.
  
 4)NOTE: PLEASE SEE 384-7 FOR PANEL LOCA-
 -TION.
  
 5)NOTE: PLEASE SEE F.H.A.R,24CFR 100.205
 FOR ALL THE REQ`MENTS OF DEVICE HEIGHTS.
 NOT ALL NOTES SHOWN ON EM-1 COMPLY.
  
 6)NOTE: PLEASE SEE LOCATION OF HWH.IN
 BATH AND MOUNTED ABOVE. THIS MUST REMAIN
 READILY ACCESS. FOR THE ELECTRICAL DISC-
 -ONNECT.
  
 7)NOTE: ALSO PLEASE NOTE GROUNDING ELEC-
 -TRODE CONDUCTOR TO BLDG STEEL AS PER
 250-50.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372