| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL |
| | EQUIPMENT. MAINS MUST BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT AS PER ARTS: |
| | 110-9/110-10 |
| | |
| | 2)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS IN NEW |
| | DWELLINGS. IF FIRE ALARM SYSTEM IS BEING |
| | INSTALLED THEN PLEASE INDICATE. |
| | |
| | 3)NOTE: PLEASE SHOW HEIGHTS OF ALL |
| | DEVICES IN UNITS. ALL MUST COMPLY WITH |
| | THE FEDERAL FAIR HOUSING ACT. |
| | 24 CFR 100.205 CHAPTER 5. |
| | |
| | 4)NOTE: PLEASE INDICATE THE DEDICTED |
| | BATH(S) CIRCUT(S) REQ`D BY 210-52D OF |
| | THE NEC.LIST ON PANEL SCHEDULE. |
| | |
| | 5)NOTE; JUST FYI,,, YOU SHOW 3/0 ON |
| | RISER DIAGRAM WHICH IS GOOD FOR 225AMPS? |
| | YOUR LOAD IS ONLY 83 AMPS AND MAIN DISC. |
| | IS 150AMPS??? YOU CAN ADJUST YOUR WIRE |
| | SIZE FOR THE 150AMP OVERCURRENT DEVICE. |
| | |
| | 6)NOTE: ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPAACE MUST BE GFI/GFI PROTECTED. |
| | AS REQ`D BY ART;210-8-A-6 |
| | PLEASE INDICATE THIS ON PLANS. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW AND APPROVAL. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL 659-8096 EXT |
| | 8372 |