Plan Review Notes
Plan Review Notes For Permit 99121294
Permit Number 99121294
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT. MAINS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT AS PER ARTS:
 110-9/110-10
  
 2)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS IN NEW
 DWELLINGS. IF FIRE ALARM SYSTEM IS BEING
 INSTALLED THEN PLEASE INDICATE.
  
 3)NOTE: PLEASE SHOW HEIGHTS OF ALL
 DEVICES IN UNITS. ALL MUST COMPLY WITH
 THE FEDERAL FAIR HOUSING ACT.
 24 CFR 100.205 CHAPTER 5.
  
 4)NOTE: PLEASE INDICATE THE DEDICTED
 BATH(S) CIRCUT(S) REQ`D BY 210-52D OF
 THE NEC.LIST ON PANEL SCHEDULE.
  
 5)NOTE; JUST FYI,,, YOU SHOW 3/0 ON
 RISER DIAGRAM WHICH IS GOOD FOR 225AMPS?
 YOUR LOAD IS ONLY 83 AMPS AND MAIN DISC.
 IS 150AMPS??? YOU CAN ADJUST YOUR WIRE
 SIZE FOR THE 150AMP OVERCURRENT DEVICE.
  
 6)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPAACE MUST BE GFI/GFI PROTECTED.
 AS REQ`D BY ART;210-8-A-6
 PLEASE INDICATE THIS ON PLANS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved