| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PROVIDE EXTERIOR ELEVATIONS FOR MODEL |
| | WITH 4 BEDROOM OPTION. |
| | 2-TRUSS LAYOUT DOESN'T INCLUDE THE |
| | ADDITIONAL BEDROOM OPTION. |
| | -UPDATE ENGINEERED TRUSS DRAWINGS. |
| | CLEARLY SPECIFY THE DESIGN CRITERIA |
| | USED IS SBC 1997 OR ASCE 7-95. |
| | 3-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOORS WITH SIDELITES ASSEMBLY, SLIDING |
| | GLASS DOORS WITH TRANSOM ABOVE |
| | ASSEMBLY, ROUND WINDOWS. |
| | 4-SEE COMMENTS ON PLANS AND REVISE/ |
| | UPDATE ALL INFORMATION AS REQUIRED. |
| | 5-FAMILY ROOM NEED TWO CEILINGS FANS |
| | (48" EACH MINIMUM). TABLE 6-6 FLORIDA |
| | ENERGY CODE, 1997 EDITION. |
| | 6-SPECIFY THE DESIGN PRESSURES AT ALL |
| | EXTERIOR OPENINGS. |
| | 7-PROVIDE COMPLETE STORM PANELS INFO |
| | UNDER A SEPARATE PERMIT. |
| | 8-ENGINEERED TRUSS DRAWINGS: |
| | -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR |
| | EACH BUILDING. REVISE AS REQUIRED. |
| | -UPDATE DESIGN CRITERIA INFORMATION. |
| | SPECIFY THE YEAR OF SBC. (1997). |
| | -CLARIFY WHY ARE THE DESIGN LOADS FOR |
| | TRUSSES D4, D3 AND CJ1 DIFFERENT THAN |
| | THE REST OF THEM. (47 PSF TOTAL,RATHER |
| | THAN 55 PSF). |
| | -ENGINEER MECHANICAL SIGNATURE IS NOT |
| | ALLOWED. ONLY WET SIGNATURE. |
| | 9-REVISE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE. MEAN ROOF |
| | HEIGHT IS 19'8" PLUS OR MINUS. SEE |
| | TABLE 1606.2A SBC 1997 FOR THE CORRECT |
| | VELOCITY PRESSURE. |