2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE EXTERIOR ELEVATIONS FOR MODEL
 WITH 4 BEDROOM OPTION.
 2-TRUSS LAYOUT DOESN'T INCLUDE THE
 ADDITIONAL BEDROOM OPTION.
 -UPDATE ENGINEERED TRUSS DRAWINGS.
 CLEARLY SPECIFY THE DESIGN CRITERIA
 USED IS SBC 1997 OR ASCE 7-95.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH SIDELITES ASSEMBLY, SLIDING
 GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY, ROUND WINDOWS.
 4-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE ALL INFORMATION AS REQUIRED.
 5-FAMILY ROOM NEED TWO CEILINGS FANS
 (48" EACH MINIMUM). TABLE 6-6 FLORIDA
 ENERGY CODE, 1997 EDITION.
 6-SPECIFY THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS.
 7-PROVIDE COMPLETE STORM PANELS INFO
 UNDER A SEPARATE PERMIT.
 8-ENGINEERED TRUSS DRAWINGS:
 -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 EACH BUILDING. REVISE AS REQUIRED.
 -UPDATE DESIGN CRITERIA INFORMATION.
 SPECIFY THE YEAR OF SBC. (1997).
 -CLARIFY WHY ARE THE DESIGN LOADS FOR
 TRUSSES D4, D3 AND CJ1 DIFFERENT THAN
 THE REST OF THEM. (47 PSF TOTAL,RATHER
 THAN 55 PSF).
 -ENGINEER MECHANICAL SIGNATURE IS NOT
 ALLOWED. ONLY WET SIGNATURE.
 9-REVISE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE. MEAN ROOF
 HEIGHT IS 19'8" PLUS OR MINUS. SEE
 TABLE 1606.2A SBC 1997 FOR THE CORRECT
 VELOCITY PRESSURE.