| Plan Review Notes For Permit 99121287 |
| Permit Number |
99121287 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. AIC RATING OF MAINS | | | NEED TO RATED FOR THE AVAILABLE FAULT | | | CURRENT. AIC RATING CAN BE FIGURED FROM | | | FAULT CURRENT CALCULATIONS. AS PER ARTS; | | | 110-9/110-10 AND 215-5 OF THE NEC. | | | | | | 2)NOTE: MISSING OUTLET IN HALL PER | | | 210-52H | | | | | | 3)NOTE:NEED TO HAVE THE DEDICATED BATH(S | | | CIRCUT LISTED ON PANEL SCHEDULE. CIRCUT | | | IS TO BE 20AMP AND #12 AWG. AS PER ART; | | | 210-52D OF THE NEC. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. AIC RATING ARE | | | TO BE ON ALL PLANS!!! THIS IS SOMETHING | | | THAT HAS BEEN PREVIOUSLY REQ`STED.IF | | | THERE ARE ANY QUESTIONS PLEASE CALL 659- | | | -8096 EXT 8372. |
|