Plan Review Notes
Plan Review Notes For Permit 99121287
Permit Number 99121287
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. AIC RATING OF MAINS
 NEED TO RATED FOR THE AVAILABLE FAULT
 CURRENT. AIC RATING CAN BE FIGURED FROM
 FAULT CURRENT CALCULATIONS. AS PER ARTS;
 110-9/110-10 AND 215-5 OF THE NEC.
  
 2)NOTE: MISSING OUTLET IN HALL PER
 210-52H
  
 3)NOTE:NEED TO HAVE THE DEDICATED BATH(S
 CIRCUT LISTED ON PANEL SCHEDULE. CIRCUT
 IS TO BE 20AMP AND #12 AWG. AS PER ART;
 210-52D OF THE NEC.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. AIC RATING ARE
 TO BE ON ALL PLANS!!! THIS IS SOMETHING
 THAT HAS BEEN PREVIOUSLY REQ`STED.IF
 THERE ARE ANY QUESTIONS PLEASE CALL 659-
 -8096 EXT 8372.