| Date |
Text |
| 2001-01-08 00:00:00 | CORRECTED BY REVISIONS3/9/00***** |
| | |
| | 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH |
| | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO |
| | BOTTOM OF ROOF STRUCTURE |
| | 2) SHT A-31 DETAIL 2 DRYER VENT TO BE |
| | MIN. 4" NOT 3", DRYER VENT TO RUN FULL |
| | LENGTH OUT OF BUILDING |
| | 3) SHT A-31 DETAIL 4 INDICATE WHICH SIZE |
| | CAP TO BE USED- 4" OR 2 1/2" NOTE: FLEX |
| | METAL DUCT NOT ALLOWED BY CODE |
| | 4) SHT AC-1 AREAS WITH 300CFM OR GREATER |
| | REQUIRES RETURN AIR FROM AREA |
| | 5) SHT AC-1 PROVIDE MANUFACTURES SPEC'S |
| | ON CAPACITY TO PUSH LENGTH OF DUCT USED |
| | 6) ANY DUCT PENETRATING RATED CEILING |
| | TO HAVE FIRE DAMPERS PER 1997 SMC 610.2 |
| | 7) CONDENSING UNIT SERVICE TO BE PER NEC |
| | AND 1997 SMC 304.7.2 WHICHEVER IS GREAT- |
| | ER. DISCONNECT TO BE WITHIN 6' OF THE |
| | SERVICE SIDE OF THE EQUIPMENT AND A 115V |
| | GFIC OUTLET REQUIRED. |
| | 8) SHT AC 5 OVERFLOW PROTECTION REQUIRED |
| | FOR AHU'S PER 1997 SMC 304.8.6 |
| | 9) BATHROOM EXHAUST DUCT SHOWN PENETRAT- |
| | ING 2ND FL CONC. FLOOR SLAB ABOVE GARAGE |
| | PROVIDE DETAIL TO SHOW COMPLIANCE W/ SMC |
| | 610.2 AND 610.4. SHAFT ENCLOSUREREQ'D |
| | FOR FIRE PROTECTION OF ASSEMBLY. |