| Plan Review Notes For Permit 99121241 |
| Permit Number |
99121241 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CORRECTED BY REVISION 3/21/00*********** | | | 1) SHT A-31 DETAIL 3 DRYER VENT AND BATH | | | EXHAUST DUCT TO BE ENCLOSED IN SHAFT TO | | | BOTTOM OF ROOF STRUCTURE. | | | 2) SHT A-31 DRYER VENT DUCT TO BE 4" NOT | | | 3". | | | 3) CONDENSATE DRAIN LINE SHALL NOT VENT | | | INTO OCCUPIED SPACE. CARRY VENT THROUGH | | | ROOF | | | 4) SHT AC-4 SHOWS DRYER VENT INTO SUB- | | | DUCT. DRYER VENT TO RUN FULL LENGTH OUT | | | OF BUILDING | | | 5) OVERFLOW PROTECTION REQUIRED FOR AHUS | | | PER 1997 SMC 304.8.6 |
|